background image

FieldPoint

 Operating Instructions

cFP-RLY-423

Four-Channel SPDT Relay Module

These operating instructions describe how to install and use the 
National Instruments cFP-RLY-423. For more information about 
configuring and accessing the cFP-RLY-423 over a network, refer 
to the user manual for the FieldPoint network module you are 
using.

Features

The cFP-RLY-423 is a Compact FieldPoint relay output module 
with the following features:

Four single-pole double-throw (SPDT) relay channels

Switches up to 1.5 A at 35 VDC or 250 VAC

LED relay status indicators

Hot swappable

–40 to 60 °C operation

250  V

rms

 maximum isolation voltage

2,300 V

rms

 transient overvoltage protection

Installing the cFP-RLY-423

The cFP-RLY-423

 

mounts on a Compact FieldPoint backplane 

(cFP-BP-

x

), which provides operating power to the module. 

Installing the cFP-RLY-423 onto a powered backplane does not 
disrupt the operation of the bank.

Summary of Contents for FieldPoint cFP-RLY-423

Page 1: ...RLY 423 is a Compact FieldPoint relay output module with the following features Four single pole double throw SPDT relay channels Switches up to 1 5 A at 35 VDC or 250 VAC LED relay status indicators...

Page 2: ...ent backward insertion 2 Press firmly to seat the cFP RLY 423 on the backplane 3 Using a number 2 Phillips screwdriver with a shank of at least 64 mm 2 5 in length tighten the captive screws to 1 1 N...

Page 3: ...peak or 60 VDC Caution Ensure that hazardous voltage wiring is performed only by qualified personnel adhering to local electrical standards Each relay channel of the cFP RLY 423 has four terminals one...

Page 4: ...loads and an external power supply to one channel of the cFP RLY 423 as shown in Figure 2 Install a 1 5 A 250 V maximum fast acting fuse suitable for the load at the connected IC terminal to protect...

Page 5: ...are connected to the relays a large counter electromotive force can occur at relay switching time because of the energy stored in the inductive load These flyback voltages can severely damage the rel...

Page 6: ...e the circuit you are planning to use Diode and Zener Diode Circuit Diode Circuit 1 This section has been reprinted with permission from American Zettler Inc Diagram Notes Use in DC applications only...

Page 7: ...hould be smaller than that of the CR circuit Do not utilize for timer loads as leakage current can cause faulty operations Circuit B is suitable for AC or DC If the load is a relay or solenoid release...

Page 8: ...Isolation and Safety Guidelines Caution Read the following information before attempting to connect the cFP RLY 423 to any circuits that may contain hazardous voltages This section describes the isola...

Page 9: ...al supply voltages the V and C terminals with other devices including other FieldPoint devices unless those devices are isolated from human contact You must connect the protective earth PE ground term...

Page 10: ...llation Category II is for measurements performed on circuits directly connected to the electrical distribution system This category refers to local level distribution such as that provided by a stand...

Page 11: ...operations min Electrical 1 105 operations at rated resistive load Maximum switching frequency Mechanical 20 operations per second Electrical 1 operation per second at maximum load Relay operate time...

Page 12: ...r altitudes the isolation voltage ratings must be lowered Pollution Degree 2 Safety This product is designed to meet the requirements of the following standards of safety for electrical equipment for...

Page 13: ...for the most current manuals examples and troubleshooting information For telephone support in the United States create your service request at ni com support and follow the calling instructions or d...

Page 14: ...0 311 210 Russia 7 095 783 68 51 Singapore 65 6226 5886 Slovenia 386 3 425 4200 South Africa 27 0 11 805 8197 Spain 34 91 640 0085 Sweden 46 0 8 587 895 00 Switzerland 41 56 200 51 51 Taiwan 886 2 252...

Page 15: ...com are trademarks of National Instruments Corporation Product and company names mentioned herein are trademarks or trade names of their respective companies For patents covering National Instruments...