15
www.climacoolcorp.com
The power for all modules is taken from a suitable circuit
breaker/fused disconnect power supply within the main
panel . The electrical service enters the individual modules
through the top into the module’s control panel enclosure .
Proper grounding of the module is mandatory . Before
carrying out any electrical work, confirm that the main
supply is isolated . A typical power wiring is located on page
28 – Power Distribution Drawing . Knockouts are provided .
Do not drill into cabinet as shavings can damage electronic
components . The power for all individual modules must be
in compliance with all local and national codes .
CoolLogic
Control System Wiring
A separate 115 volt power supply is required to power the
CoolLogic
master control panel . Communication between
the master control panel and chiller modules requires a
simple two-conductor 22 AWG shielded cable rated at 60°C
minimum, daisy chain connection .
Control wiring cannot be
installed in the same conduit as line voltage wiring or with
wires that switch highly inductive loads such as contactor
and relay coils.
Refer to the Power Distribution Drawing on
page 28 of this manual for more information . All wiring must
be in compliance with all local and national codes .
ARC156 Wiring Specifications
The table on the next page lists the specifications for
ARC156 wiring . The wire jacket and UL temperature rating
specifications provide two acceptable alternatives. Halar
has a higher temperature rating and a tougher outer jacket
than SmokeGard, and it is appropriate for use in applications
where there are concerns about abrasion . Halar is also less
likely to crack in extremely low temperatures .
NOTE:
Use the specified type of wire and cable for
maximum signal integrity .
Electrical Phase Sequencing
Proper clockwise rotation for scroll compressor motors
is important to prevent damage to the compressors .
ClimaCool recommends the use of a phase sequence
indicating instrument following the manufacturers
directions . An alternative is to “bump test” the compressors
one at a time with pressure gauges attached to the high and
low gauge ports of the compressors to check for proper
rotation . Energize the compressor for a few seconds to
ensure the discharge pressure gauge increases significantly.
If the discharge pressure does not increase, proper
rotation is reversed . Compressor rotation can be reversed
by opening the main electrical disconnect and switching
any two of the main power supply leads feeding that
compressor’s contactor .
Proper Voltage Balance
Occasionally, in three phase circuits, a voltage imbalance
occurs between phases . It is not recommended to operate
equipment when an imbalance greater that 2% occurs . This
causes motors to run at high temperatures and may affect
their longevity . The following example describes how to
calculate the average voltage of the three phases to see if
the imbalance is greater than 2% .
Example:
Line 1 = 226v Line 2 = 230v Line 3 = 228v
The average is: (226+230+228) / 3 = 228v
Next, [100(228-226)] / 228 = 0 .9%
The voltage imbalance of the three phase circuit is 0 .9% .
This is well under the 2% range .
Voltage/Phase Monitor
Voltage/phase monitors are factory supplied for field
installation with the
CoolLogic
Master Control Panel . The
voltage/phase monitor helps guard the chiller bank against
voltage fluctuations, phase failure or phase reversal
conditions which could void the warranty . The voltage/
phase monitor has three wires that connect to the main
three phase power chiller bank input . Two low voltage
control wires are connected to the
CoolLogic
Master Control
Panel . Do not install control wiring in the same conduit
as line voltage wiring or with wires that switch highly
inductive loads such as contactor and relay coils .
Note: It
is mandatory to install one (1) monitor per bank at main
power distribution panel to monitor voltage and phasing of
power to the modules. See Wiring Diagram on page 17.
Electrical Connection
CAUTION/ATTENTION
Use only copper conductors for field
installed wiring. Unit terminals are
not designed to accept other types of
conductors.
Utilisez uniquement des conducteurs en
cuivre pour le câblage. Bornes de l’unité
ne sont pas conçus pour accepter
d’autres types de conducteurs.
WARNING/ADVERTISSEMENT
Disconnect power supply(ies)
before servicing. Refer servicing
to qualified service personnel.
Electric shock hazard. May
result in injury or death!
Debrancher avant d’entreprendre
le dépannage de l’appareil.
Consulter un réparateur qualifie
pour le dépannage. Risque de
choc électrique. Résiltat de mai
dans dommages ou la mort!
CAUTION/ATTENTION
Unit to be serviced by qualified
personnel only. Refrigerant
system under pressure. Relieve
pressure before using torch.
Recover refrigerant and store or
dispose of properly.
Conifer la maintenance à un
technicien qualifie. Le systéme
frigorifique sous pression.
Décomprimer avant d’exposer
à la flamme. Récuperer le
frigorigene et le stocker ou le
détrulre correctement.
Summary of Contents for CLIMACOOL UCR 30
Page 19: ...17 www climacoolcorp com Voltage Phase Monitor Wiring Diagram...
Page 29: ...27 www climacoolcorp com Evaporator Water Pressure Drop Charts...
Page 30: ...28 www climacoolcorp com Glycol Performance Adjustments Factor Charts...
Page 78: ...76 www climacoolcorp com Wiring Diagram...
Page 79: ...77 www climacoolcorp com Wiring Diagram...
Page 80: ...78 www climacoolcorp com Wiring Diagram CoolLogic Control Panel...
Page 81: ...79 www climacoolcorp com Wiring Diagram CoolLogic Control Panel...