POWER CONNECTION
Line voltage connection is made by connecting the incoming
line voltage wires to the “L” side of the contactor as shown in
Figure 21. Consult Tables 5a and 5b for correct fuse size.
208 VOLT OPERATION
All residential 208-230 Volt units are factory wired for 230
Volt operation. The transformer may be switched to the 208V
tap as illustrated on the wiring diagram by switching the red
(208V) and the orange (230V) wires at the contactor terminal.
ACCESSORY CONNECTIONS
A terminal paralleling the compressor contactor coil has been
provided on the DXM2.5 control. Terminal “A” is designed
to control accessory devices.
NOTE: This terminal should
be used only with 24 Volt signals and not line voltage.
Terminal “A” is energized with the compressor contactor
(see Figure 26).
The DXM2.5 controller includes two accessory relays ACC1
and ACC2. Each relay includes a normally open (NO) and
a normally closed (NC) contact. Accessory relays may be
configured to operate as shown in Tables 6 and 7.
Electrical – Low Voltage Wiring
Low Voltage Field Wiring
P1
Alarm
Relay
Comp
Relay
O
Y1
Y2
W
G
C
R
AL1
24Vdc
EH1
EH2
P6
R
C
Off On
JW3
A
OVR
ESD
C
R
NSB
AL2
JW1
Acc1
Relay
Acc2
Relay
H
COM1
NC1
NO1
COM2
NC2
NO2
P3
CO
RV
RV
LT1
LT1
LT2
LT2
LP
LP
HP
HP
P7
Status
Fault
R
R
CC
CCG
CO
S1
S2
1
12
1
4
es
U
yr
ot
ca
F
(240Vac)
Com
N.O.
Fan Enable
7"
Micro
U1
Off On
P2
COH
COM
AO2
P11
Gnd
T1
P10
T2 T2 T3 T3 T4 T4
T5
P9
T5 T6 T6
A0-1 A0-2
Off On
S3
RV
Relay
CCH
Relay
Test
P5
B-
Gnd
P4
A+ 24V
(240Vac)
Fan Speed
N.O.
N.C.
12V
OUT
Gnd
P8
IN
NC
P12
1 2 3 4
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Accessory
Relays
Accessory
Terminal
Figure 25: Tranquility
®
Low Voltage Field Wiring
Table 10: Accessory Relay 2 Configuration
Table 9: Accessory Relay 1 Configuration
DIP 2.1
DIP 2.2
DIP 2.3
ACC1 Relay Option
ON
ON
ON
Cycle with fan
OFF
ON
ON
N/A for Residential Applications
ON
OFF
ON
Water valve – Slow opening
ON
ON
OFF
Outside air damper
OFF
ON
OFF
ClimaDry
®
II option – Dehumidistat
OFF
OFF
OFF
ClimaDry
®
II – Humidistat
OFF
OFF
ON
N/A for Residential Applications
ON
OFF
OFF
N/A for Residential Applications
All other DIP combinations are invalid
DIP 2.4
DIP 2.5
DIP 2.6
ACC2 Relay Option
ON
ON
ON
Cycle with compressor
OFF
ON
ON
N/A for Residential Applications
ON
OFF
ON
Water valve – Slow opening
OFF
OFF
ON
Humidifier
ON
ON
OFF
Outside air damper
All other DIP combinations are invalid
Figure 26: Accessory Connections