Troubleshooting Form
Note: Never connect refrigerant gauges during startup procedures. Conduct water-side analysis using P/T ports to determine
water flow and temperature difference. If water-side analysis shows poor performance, refrigerant troubleshooting may be
required. Connect refrigerant gauges as a last resort.
Refrigerant Circuit Diagram
Packaged Water-to-Air
RP929
Troubleshooting Form
Customer:
Loop Type:
Startup Date:
Model #:
Serial #:
Antifreeze Type & %:
Complaint:
Description
Heating
Cooling
Notes
Water Side Analysis
1 Water In Temp.
2 Water Out Temp.
Temp. Diff . =
3
Water In Pressure
4 Water Out Pressure
4a Pressure Drop
4b GPM
Heat of Extraction (Absorption) or Heat of Rejection:
HE or HR (Btuh) =
Enter HE or HR:
Flow Rate (GPM) x
Temp. Diff (deg F) x
Fluid Factor
Refrigerant Analysis
5
Suction Temp.
6 Suction Pressure
6a
Saturation Temp.
6b
Superheat
7
Discharge Temp.
8 Discharge Pressure
8a
Saturation Temp.
8b Subcooling
9
Liquid Line Temp
10 Return Air Temp.
11 Supply Air Temp.
Temp. Diff . =
Voltage
Compress Amps
COMPRESSOR
DISCHARGE
SUCTION
HWG**
AIR
COIL
EXPANSION
VALVE
FILTER
DRIER*
REVERSING
VALVE
HEATING POSITION
5
COAX
11
4
2
3
1
8
7
6
9
LT2:
HEATING
LIQUID
LINE
CONDENSER (HEATING)
EVAPORATOR (COOLING)
CONDENSER (COOLING)
EVAPORATOR (HEATING)
* Filter drier not used
for some R-22 units.
** Turn off HWG before
troubleshooting.
REFRIG FLOW - HEATING
REFRIG FLOW - COOLING
Source
COOLING POSITION
9
LT1:
COOLING
LIQUID
LINE
10
REFRIGERANT:
R-22
R-410A
OPERATING MODE:
HEATING
COOLING
Fluid Factor:
500 (Water); 485 (Antifreeze)