Horizontal Installation, Cont’d.
Figure 8: Right Return Side to Back
Figure 7: Left Return Side to Back
Field Conversion of Air Discharge
OVERVIEW
Horizontal units can be field converted between side (straight)
and back (end) discharge using the instructions below.
NOTE:
It is not possible to field convert return air
between left or right return models due to the
necessity of refrigeration copper piping changes.
PREPARATION
It is best to field convert the unit on the ground before
hanging. If the unit is already hung it should be taken down
for the field conversion.
SIDE TO BACK DISCHARGE CONVERSION
1. Place unit in well lit area. Remove the screws as shown
in Figure 8 to free top panel and discharge panel.
2. Lift out the access panel and set aside. Lift and rotate
the discharge panel to the other position as shown,
being careful with the blower wiring.
3. Check blower wire routing and connections for tension
or contact with sheet metal edges. Reroute if necessary.
4. Check refrigerant tubing for contact with
other components.
5. Reinstall top panel and screws noting that the location
for some screws will have changed.
6. Manually spin the fan wheel to ensure that the wheel is
not rubbing or obstructed.
7. Replace access panels.
BACK TO SIDE DISCHARGE CONVERSION
If the discharge is changed from back to side, use above
instruction noting that illustrations will be reversed.
LEFT VS. RIGHT RETURN
It is not possible to field convert return air between left or right
return models due to the necessity of refrigeration copper
piping changes. However, the conversion process of side to
back or back to side discharge for either right or left return
configuration is the same. In some cases, it may be possible to
rotate the entire unit 180 degrees if the return air connection
needs to be on the opposite side. Note that rotating the unit
will move the piping to the other end of the unit.