General
This accessory is used when
F1145/F1245/F1345/F370/F470/F750/VVM500 is installed
in houses with up to four different climate systems that
require different flow line temperatures, for example, in
cases where the house has both a radiator system and
an under floor heating system.
The water flow in the climate systems together should
not exceed 1700 l/h.
Caution
Underfloor heating systems are normally
max
flow line temperature
set between 35 and 45
°C.
Check the max temperature for your floor with
your floor supplier.
Caution
If the room sensor is used in a room with under
floor heating it should only have an indicatory
function, not control of the room temperature.
Contents
Cable ties
4 x
Circulation pump
1 x
Shunt motor
1 x
3-way valve
1 x
Kit for accessory card
1 x
Heating pipe paste
2 x
Aluminium tape
1 x
Insulation tape
1 x
Replacement gasket
2 x
Temperature sensor
2 x
Room sensor
1 x
Pipe with straight coupling*
1 x
* This is only used when connecting to NIBE F370 or
F470.
Component positions
LEK
AA5-X4
AA5-S2
AA5-X2
AA5-X9
X1
FA1
AA5-F1
AA5
Electrical components
Miniature circuit-breaker. 10A
FA1
Terminal block, power supply
X1
Accessory card
AA5
Terminal block, sensors and external
blocking
AA5-X2
Terminal block, communication
AA5-X4
Terminal block, circulation pump, mixing
valve and auxiliary relay
AA5-X9
DIP switch
AA5-S2
Fine wire fuse, T4AH250V
AA5-F1
Designations in component locations according to
standard IEC 81346-1 and 81346-2.
14
English, Installer manual - ECS 40/ECS 41
GB