C. Display

In normal mode the display shows:

WW-out: The current heating/brine temperature (the
temperature of the water coming out of the heat
pump).

Hot water: Actual hot water temperature (accessory,
when docking).

1

D. Indicator lamps

Room heating/cooling

VB-Fram 49 (50) °C

Varmvatten

51 °C

– Shows room heating/cooling is allowed when lit
(circulation pump in operation).

Heat pump

VB-Fram 49 (50) °C

Varmvatten

51 °C

–Shows the compressor is running when lit.

Hot water (accessory)

VB-Fram 49 (50) °C

Varmvatten

51 °C

–A steady light shows that hot water charging is in
progress.

–Flashes rapidly when temporary increase of the hot
water temperature is selected (approx. 60°C during
24 hours).

–Flashes slowly when periodic increase of the hot water
temperature is selected (approx. 60°C in accordance
with the selected interval).

External additional heat

VB-Fram 49 (50) °C

Varmvatten

51 °C

– A steady light means that the external additional
heating is on.

– Flashes slowly when external additional heat is allo-
wed.

– Rapid flashing means that only external additional
heating is on.

Alarm

VB-Fram 49 (50) °C

Varmvatten

51 °C

Flashes rapidly when a fault has occurred.

E. Increase/reduce room temperature

The "Increase/reduce room temperature" knob raises or
lowers the room temperature (changes the temperature of

"WW-out"

)

Setting different operating modes (also with
accessories)

VB-Fram 49 (50) °C

Varmvatten

51 °C

Normal mode (basic setting):

Addition ready to

start if needed. Hot water charging cuts in if needed.

LEDs:

Continuous light

Room heating/coo-
ling:

Continuous light during hot water char-
ging

Hot water:

Flashing / Steady light

Additional heat:

Position ”No additional heat”:

Press the ”Operating mode”

button again.

LEDs:

Continuous light

Room heating/coo-
ling:

Continuous light during hot water char-
ging

Hot water:

Not lit

Additional heat:

Press the ”Operating mode” button again.

Press the ”Operating mode” button again.

”No room heating/cooling mode” (only hot water):

Press the ”Operating mode” button again.

LEDs:

Not lit

Room heating/coo-
ling:

Continuous light during hot water char-
ging

Hot water:

Not lit

Additional heat:

The system returns to normal mode the next time the ”Op-
erating mode” button is pressed.

VB-Fram 49 (50) °C

Varmvatten

51 °C

(

Note!

Requires external additional heater.)

Normal mode:

No raised hot water temperature ac-

tivated.

Temporarily raised hot water temperature:

Press the

”Extra HW” button once. A raised hot water temperature is
obtained for 24 hours. The ”Hot water” LED flashes rapidly.
Lit during charging.

Periodically raised hot water temperature:

Press the

”Extra HW” button again. The hot water temperature is
raised as shown on menu 13. The ”Hot water” LED flashes
slowly. Lit during hot water charging.

The next time the ”Extra hot water” button is pressed, the
system returns to normal mode.

5

FIGHTER 1127

For Home Owners

Front panel

Summary of Contents for FIGHTER 1127

Page 1: ...INSTALLATION AND MAINTENANCE INSTRUCTIONS MOS GB 0737 2 FIGHTER 1127 031153 FIGHTER 1127 2 0 2 1 R 0 LEK...

Page 2: ...LEK LEK LEK LEK LEK LEK LEK LEK LEK LEK...

Page 3: ...n of room temperature sensor RG 20 17 Connecting the outside sensor 17 Connecting the supplied hot water temperature sensor with floating condensing 18 Connecting supplied external circulation pumps 1...

Page 4: ...ominal temperature diff 2 5 C Temperature heat medium in out ____ ____ Pump setting ___ Nominal temperature diff 5 10 C Settings Basic setting Menu Basic setting Menu 60 10b HP min 2 Room 300 10b Add...

Page 5: ...n of flow changes in the refrigerant system Even the external systems brine and heating medium change direction by the external pumps starting for opposite circulation The heat energy is now emitted t...

Page 6: ...p and additional heater when necessary if the latter is fitted B Function keys Channel Selection of the window menu VB Fram 49 50 C Varmvatten 51 C Increase Increase of current value VB Fram 49 50 C V...

Page 7: ...g Addition ready to start if needed Hot water charging cuts in if needed LEDs Continuous light Room heating coo ling Continuous light during hot water char ging Hot water Flashing Steady light Additio...

Page 8: ...om temperature Changing the room temperature manually If you want to temporarily or permanently increase or lower the indoor temperature in relation to the previous heat set ting turn the Increase red...

Page 9: ...ated flow temperature Hot water Indication of the hot water temperature 2a Outdoor 14 C Room 20 5 20 C Outdoor Current outdoor temperature Room Current room temperature Only shown if a room sensor is...

Page 10: ...eating Press the Channel button to continue 4b WW in 37 53 C HW stop 52 C This menu is a sub menu to menu 4 Setting HW stop Press the Increase button in menu 4a A cursor will ap pear within the bracke...

Page 11: ...max levels Sensor placement and pump flow observed 7 HP start 10 HP off HP start Counts the starts of the heat pump cumulative HP off Shows the operating mode HP off HP on HP start in X minutes or Hi...

Page 12: ...nsors The room sensor is used to compensate the deviation in room temperature Guideline values for collectors Recommended collector length must be adjusted according to local conditions The length of...

Page 13: ...by the system is obtained Settings 10a GM GM Degree min P Current value for number of degree minutes For example this value can be changed to accelerate the start of heating cooling production Settin...

Page 14: ...re is then supplemented with EP Selectable operating modes Compressor operation 0 1 step EP drift after acknowledgement 1 16 Cal Out 0 Room 0 Brine In 0 Brine O 0 Cal Out P Calibration of outside sens...

Page 15: ...stops at half R C below Ex ample At R 2 at FIGHTER 1127 and 22 C on RG 20 cooling starts at 24 C and stops at 23 C Default setting is Off In cooling mode with the room sensor RG20 select Cooling On Th...

Page 16: ...ilable pressure setup 0 20 80 40 Fl de 60 1 0 k W 0 20 80 40 Fl de 60 100 100 0 0 07 0 13 0 21 l s 0 27 0 35 0 42 0 48 0 69 0 62 0 55 0 0 07 0 13 0 21 l s 0 27 0 35 0 42 0 48 0 69 0 62 0 55 1 2 3 1 2...

Page 17: ...k VVB ACK is fully charged the shuttle valve VXV switches over to the heating circuit The heat pump is then controlled by the outdoor sensor in combination with the built in flow sensor and room tempe...

Page 18: ...tallation and wiring must be carried out in accord ance with the stipulations in force Supply cables to the heat pump are placed in the cable duct on the left of the unit Cables for external sensors m...

Page 19: ...e for example by placing in a niche between shelves behind a curtain above or close to a heat source or the like Also consider any draughts from exterior doors Neither must the unit be affected by sol...

Page 20: ...rated 22 156 156 X7 Connection of accessory VST 12 Connect the accessory VST 12 to the terminal block X6 6 positions 2 to 5 as illustrated 6 X6 F1127 mitsubishi A 22 21 30 Connection of flow monitor F...

Page 21: ...ling pump are now operating together Let the liquid circu late via the mixing vessel until there are no more air bubbles in the liquid in the return hose Now stop the brine pump by resetting Brine pum...

Page 22: ...lar attention should be given to the level in the brine system when initially using the heat pump Some topping up may be necessary 9 Read the heating medium temperatures WW out and WW in The differenc...

Page 23: ...10 9 8 7 6 5 4 3 2 1 1514 13 12 11 10 8 7 6 5 4 3 2 1 40 C UTETEMPERATUR 10 0 10 5 5 30 40 50 60 70 C FRAMLEDNINGSTEMPERATUR 20 30 F RSKJUTNING V RMEKURVA 2 9 V RMEKURVA V RMEKURVA 5 5 F RSKJUTNING V...

Page 24: ...positions 2 0 2 1 R 0 LEK F1127 mitsubishi AK 8kW 95 68 6 22 9 21 30 29 26 13 97 14 2 K E L K E L 4 86 71 70 89 5 94 35 77 76 16 96 87 LEK 18 17 153 41 33 27 42 7 48 49 65 65 19 FIGHTER 1127 22 Misce...

Page 25: ...Service connection low pressure 42 Expansion valve heating mode 48 Expansion valve cooling mode 49 Safety valve collector side 52 Particle filter 63 Drying filter 65 Contactor compressor start 68 Conn...

Page 26: ...Electrical circuit diagram FIGHTER 1127 24 Miscellaneous Technical specifications...

Page 27: ...25 FIGHTER 1127 Miscellaneous Technical specifications...

Page 28: ...FIGHTER 1127 26 Miscellaneous Technical specifications...

Page 29: ...27 FIGHTER 1127 Miscellaneous Technical specifications...

Page 30: ...98 100 100 100 30 100 67 5 4 71 70 2 0 2 1 R 0 HM flow 49 50 C Hot water 51 C 598 525 525 625 2 0 2 1 R 0 HM flow 49 50 C Hot water 51 C 30 50 1000 75 198 100 100 100 30 100 67 Leave space free to the...

Page 31: ...59526447 230V HEJSAN PC 0017NIB DK 50Hz IP 44 TF 110 Class H Max 10bar 2 5uF 45 0 20 65 0 30 90 0 40 1m A P W LEK GRUNDFOS Type UPS 25 60 130 P N 59526447 230V HEJSAN PC 0017NIB DK 50Hz IP 44 TF 110...

Page 32: ...W Power external circulation pumps 35 28 mm Connection Brine male 28 mm Connection heating medium male 1 9 1 79 kg Refrigerant quantity R407C 0 65 0 48 l s Brine flow 15 23 kPa Pressure drop evaporato...

Page 33: ...ing Incorrect setting of the Curve slope and or Increase reduce room temperature Cause Adjust the setting Action NOTE The product s serial number should always be stated with all correspondence with N...

Page 34: ...low pressure or ice if ice has formed the brine pump 35 will be warm Cause Vent and top up the fluid Wait a few hours Action Brine pump 35 not running Cause Check the brine pump Action Lack of heatin...