12

Subject to Technical Modifications of GV-HR110

Turn off the facility

No lamps are lit on the service panel, even when you press on

both buttons.

Error:

-  A fuse has blown in the fuse box, no power supply to the facility.

-  One of the fuses on the circuit board has shorted.

-  Loose contact, no voltage to the aggregate.

-  Loose contact between the aggregate and control panel.

Red light constantly lit on the control panel:

Error for control:

-  Frost thermostat switched off. (Facilities with water heaters.)

-  Faulty sensor in aggregate

-  Faulty sensor in control panel

-  If no sensor is attached for incoming air it has been replaced

  by a resistor that is faulty

-  Loose sensor wire or loose bridge in coupling list on the circuit  

board.

Condensation flowing from the aggregate:

Error:

-  Condensation drain fouled with dirt

-  No water in the waterseal

-  Condensation drain fouled due to frost.

-  Drain is not sufficiently protected from frost

No incoming air to the residence:

Error:

-  Faulty fan

-  Fouled incoming air filter

-  Fouled outside air grid

-  A fuse has blown on the circuit board

-  No power supply to the facility

No exhaust air from the residence:

Error:

-  Faulty fan

-  Fouled filter

-  A fuse has blown on the circuit board

Cold incoming air

Error:

-  Counter-flow heat exchanger is fouled with dirt or ice.

-  Faulty exhaust fan

-  Fouled exhaust air filter

-  An electric postheater is disconnected due to overheating

  protection (Only facilities with electric postheaters mounted).

-  No circulation of hot water to the waterborne postheater. 

  (Only facilities with mounted waterborne postheaters).

-  Fouled circulation pump, air in the hot water pipe, faulty

  thermostat/motor valve, faulty setting of control panel.

Display message:

Computer error:

-  no connection with circuit board

-  lead too long between display and circuit card

Version error:

-  Program displayed and circuit card not compatible

Exchange filter:

-  Filter must be changed

Stop ON-OFF:

-  Filter has not been exchanged/cleaned within 14 days 

from the filter alarm being triggered. 

  The facility is turned off.

Troubleshooting

Summary of Contents for GV-HR110

Page 1: ...k NIBE A S Sverigesvej 6 DK 6100 Haderslev Tlf 45 7353 2700 www NIBE dk NIBE AB Sweden Box 14 Hannabadsv gen 5 SE 285 21 Markaryd www NIBE eu INSTALLATIONS MANUAL Passive ventilation Heat recovery GV...

Page 2: ...tics 7 Insulating ducts in warm rooms 8 Reheating of the supply air 8 Electric installations 9 Control and settings of the facility 9 Optimal adjustment of the facility 9 Facility maintenance 10 Troub...

Page 3: ...a thermostat and an electric heating element that switches on when the temperature falls below 2 C IMPORTANT IMPORTANT IMPORTANT IMPORTANT 7 Set the amount of incoming 1 and outgoing air before using...

Page 4: ...r 10 El kasse 11 Kondensvandsbakke 12 Kondensvandsafl b 13 230V 50Hz 14 By pass 2 4 13 72 7 60 7 550 42 1014 24 32 1088 1056 550 135 280 4 Subject to Technical Modifications of GV HR110 GV HR110 Assem...

Page 5: ...in the picture A A Visible wall mountings Concealed wall mountings Cabinet assembly gummif dder som leveret ved vandret montage af maskinen skal de leverede gummif dder flyttes til positioner som anvi...

Page 6: ...he condensation drain side The waterseal must be airtight e g by bending a 15 mm copper pipe as a waterseal see the drawing on the left A reinforced water hose is attached between the drain connection...

Page 7: ...even thicker insulation to avoid warm air in the attic from heating the incoming air during the summer Make sure that the closures are tight where the exhaust air duct comes through the roof or throu...

Page 8: ...ated in menu 4 5 User menu and that the setpoint temperature is set in menu 4 8 Service Menu Recommended setpoint is 3 C Reheating of the supply air Since the counterflow heat exchanger cannot recycle...

Page 9: ...ectly mounted with a waterseal and that it is protected from frost Pour 1 litre of water into the condensation container and check that it flows unimpeded through the condensation drain pipe 5 Set all...

Page 10: ...the procedure both knobs must be turned one quarter turn clockwise to the right When the filter has been exchanged or cleaned by shaking them to remove most of the dirt the filter timer is set by pre...

Page 11: ...amage the plates The effect will no longer be optimal if the plates are damaged Fans Remember to switch of the power supply Check the fans in the fan wheel for dirt every third year The four outermost...

Page 12: ...st No incoming air to the residence Error Faulty fan Fouled incoming air filter Fouled outside air grid A fuse has blown on the circuit board No power supply to the facility No exhaust air from the re...

Page 13: ...Belimo Bypass 230VAC H7 R10 Fan extract air 230VAC H8 R12 ON OFF Bypass 2x230VAC H9 R10 Fan supply air 230VAC bypass H16 R8 AUX relay 230VAC max 20W H17 R9 AUX relay 230VAC max 20W 1 1 1 1 1 1 1 1 1 1...

Page 14: ...Brown Brown Blue Blue Yellow green Yellow green Water valve Belimo Bypass Humidity sensor White Red Blue EC fan Supply air Aux relay R8 1x230V 50Hz ONLY control current Red Brown Blue Green Yellow Wh...

Page 15: ...dards hergestellt Directive a Machinery 2006 42 EC 15 March 2006 b Low Voltage 2006 95 EU 12 December 2006 c Electromagnetic Compatibility 2004 108 EC 15 December 2004 d Radio Telecommunication 99 5 E...

Page 16: ...294 71 Benatky nad Jizerou Tel 420 326 373 801 Fax 420 326 373 803 E mail nibe nibe cz www nibe cz PL NL FI DK DE CZ NIBE Energy Systems OY Juurakkotie 3 01510 Vantaa 3C Broom Business Park Bridge Wa...

Reviews: