background image

3 m

1 m

3 m

7

Subject to Technical Modifications of GV-HR110

Isolering af kanaler, alt. A

Isolering af kanaler, alt. B

Forkert isolering af kanaler

Insulating ducts in cold rooms

If you want to make use of the aggregate‘s high recycling

rate (efficacy), the ducts must be insulated correctly.

Incoming and outgoing air ducts:

To reduce heat loss from the duct system in cold attics the

ingoing and outgoing air ducts must be insulated with

at least 100 mm insulation. If the insulation alternative A is

used, we recommend the insulating be done with 2 times

50 mm plate covers with paper or aluminium foil on the

outside and overlaying joints between the 2 insulation

layers. If the ducts are laid out on the roof rafters, then

alternative B can be used. The insulation must always be

packed tightly around the pipes.

Outside air and exhaust air ducts in cold rooms:

Outside air and exhaust air ducts must be insulated with

PE30-insulation. The outside air ducts can be insulated

with even thicker insulation to avoid warm air in the attic

from heating the incoming air during the summer.

Make sure that the closures are tight where the exhaust

air duct comes through the roof or through the gable so

that damage from condensation is avoided.

Duct system

We recommend that the duct system be made of 

spiralflanged pipes and couplings made with rubber  

ring seals to assure a sealed, durable duct system.

To assure a satisfactory low aggregate noise level, always

mount an exhaust silencer on the ingoing and outgoing

duct system between the aggregate and the first ingoing

and outgoing units.

We recommend dimensioning the air speeds in the ducts

sufficiently low so that no noise occurs from the ingoing

and outgoing air units.

When placing the outgoing air and exhaust hood/grid

make sure that the two air flows are not short-circuited

thereby avoiding the outgoing air being sucked in again.

We recommend placing a grid on the north or east side of

the house for optimal comfort in the residences/flats.

Minimum distance: 3 metres between the outside air intake

and exhaust air.

Insulation of ducts alt. A

Incorrect insulation of ducts

Insulation of ducts, alt. B

Summary of Contents for GV-HR110

Page 1: ...k NIBE A S Sverigesvej 6 DK 6100 Haderslev Tlf 45 7353 2700 www NIBE dk NIBE AB Sweden Box 14 Hannabadsv gen 5 SE 285 21 Markaryd www NIBE eu INSTALLATIONS MANUAL Passive ventilation Heat recovery GV...

Page 2: ...tics 7 Insulating ducts in warm rooms 8 Reheating of the supply air 8 Electric installations 9 Control and settings of the facility 9 Optimal adjustment of the facility 9 Facility maintenance 10 Troub...

Page 3: ...a thermostat and an electric heating element that switches on when the temperature falls below 2 C IMPORTANT IMPORTANT IMPORTANT IMPORTANT 7 Set the amount of incoming 1 and outgoing air before using...

Page 4: ...r 10 El kasse 11 Kondensvandsbakke 12 Kondensvandsafl b 13 230V 50Hz 14 By pass 2 4 13 72 7 60 7 550 42 1014 24 32 1088 1056 550 135 280 4 Subject to Technical Modifications of GV HR110 GV HR110 Assem...

Page 5: ...in the picture A A Visible wall mountings Concealed wall mountings Cabinet assembly gummif dder som leveret ved vandret montage af maskinen skal de leverede gummif dder flyttes til positioner som anvi...

Page 6: ...he condensation drain side The waterseal must be airtight e g by bending a 15 mm copper pipe as a waterseal see the drawing on the left A reinforced water hose is attached between the drain connection...

Page 7: ...even thicker insulation to avoid warm air in the attic from heating the incoming air during the summer Make sure that the closures are tight where the exhaust air duct comes through the roof or throu...

Page 8: ...ated in menu 4 5 User menu and that the setpoint temperature is set in menu 4 8 Service Menu Recommended setpoint is 3 C Reheating of the supply air Since the counterflow heat exchanger cannot recycle...

Page 9: ...ectly mounted with a waterseal and that it is protected from frost Pour 1 litre of water into the condensation container and check that it flows unimpeded through the condensation drain pipe 5 Set all...

Page 10: ...the procedure both knobs must be turned one quarter turn clockwise to the right When the filter has been exchanged or cleaned by shaking them to remove most of the dirt the filter timer is set by pre...

Page 11: ...amage the plates The effect will no longer be optimal if the plates are damaged Fans Remember to switch of the power supply Check the fans in the fan wheel for dirt every third year The four outermost...

Page 12: ...st No incoming air to the residence Error Faulty fan Fouled incoming air filter Fouled outside air grid A fuse has blown on the circuit board No power supply to the facility No exhaust air from the re...

Page 13: ...Belimo Bypass 230VAC H7 R10 Fan extract air 230VAC H8 R12 ON OFF Bypass 2x230VAC H9 R10 Fan supply air 230VAC bypass H16 R8 AUX relay 230VAC max 20W H17 R9 AUX relay 230VAC max 20W 1 1 1 1 1 1 1 1 1 1...

Page 14: ...Brown Brown Blue Blue Yellow green Yellow green Water valve Belimo Bypass Humidity sensor White Red Blue EC fan Supply air Aux relay R8 1x230V 50Hz ONLY control current Red Brown Blue Green Yellow Wh...

Page 15: ...dards hergestellt Directive a Machinery 2006 42 EC 15 March 2006 b Low Voltage 2006 95 EU 12 December 2006 c Electromagnetic Compatibility 2004 108 EC 15 December 2004 d Radio Telecommunication 99 5 E...

Page 16: ...294 71 Benatky nad Jizerou Tel 420 326 373 801 Fax 420 326 373 803 E mail nibe nibe cz www nibe cz PL NL FI DK DE CZ NIBE Energy Systems OY Juurakkotie 3 01510 Vantaa 3C Broom Business Park Bridge Wa...

Reviews: