Subject to Technical Modifications of GV-HR110

Insulation of ducts in warm rooms

Supply air and extract air ducts:

Supply air and extract air ducts installed in heated rooms 

of the residence do not need to be insulated unless 

they are used for cooling, bypass or ground source 

heat exchanger. In this case, the supply air duct is to be 

insulated.

Fresh air and exhaust air ducts:

If the fresh air and exhaust air ducts are installed in a 

heated space they must be insulated equivalent to at 

least PE30 insulation. 

When using ground source heat exchangers we 

recommend 100 mm insulation on the fresh air duct.

Preheating of the fresh air

The supplied electric preheater is to be installed on 

the fresh air duct and connected to the terminal block 

H3. The AHU‘s built-in fresh air sensor (T3) is to be 

disconnected from terminal L3, pos. 3 and 4, and 

replaced with the supplied fresh air sensor. This fresh air 

sensor is to be installed approx. 500 mm in front of the 

electric preheater to avoid the impact of radiant heat. 

It is important that the preheater is activated in menu 4.5 

User menu and that the setpoint temperature is set in 

menu 4.8 Service Menu. Recommended setpoint is -3 °C.

Reheating of the supply air

Since the counterflow heat exchanger cannot recycle 

all heat from the exhaust air to the incoming air, the 

supply air will be approx. 1-4 °C lower than the room 

temperature of the residence during the winter season.  

If you want to use the facility for heating, you can mount  

a water-based or electric reheater that can heat the

incoming air to room temperature.

Water based reheater:

To protect the water based reheater from frost damages, 

it must be equipped with a frost sensor and it must be 

insulated. The frost sensor is mounted behind the plates 

of the water-based reheater. The sensor that controls the 

motor valve is mounted in the supply air duct approx. 500 

mm behind the water-based reheater so that it will not 

be affected by the radiant heat from the heating element. 

The water connection to the water based reheater must 

be performed by an authorised sanitary and heating 

installer.

Electric reheater:

The control sensor for the electric reheater is mounted

in the supply air duct approx. 500 mm behind the electric 

reheater so that it will not be affected by the radiant heat 

from the heating element.

Summary of Contents for GV-HR110

Page 1: ...k NIBE A S Sverigesvej 6 DK 6100 Haderslev Tlf 45 7353 2700 www NIBE dk NIBE AB Sweden Box 14 Hannabadsv gen 5 SE 285 21 Markaryd www NIBE eu INSTALLATIONS MANUAL Passive ventilation Heat recovery GV...

Page 2: ...tics 7 Insulating ducts in warm rooms 8 Reheating of the supply air 8 Electric installations 9 Control and settings of the facility 9 Optimal adjustment of the facility 9 Facility maintenance 10 Troub...

Page 3: ...a thermostat and an electric heating element that switches on when the temperature falls below 2 C IMPORTANT IMPORTANT IMPORTANT IMPORTANT 7 Set the amount of incoming 1 and outgoing air before using...

Page 4: ...r 10 El kasse 11 Kondensvandsbakke 12 Kondensvandsafl b 13 230V 50Hz 14 By pass 2 4 13 72 7 60 7 550 42 1014 24 32 1088 1056 550 135 280 4 Subject to Technical Modifications of GV HR110 GV HR110 Assem...

Page 5: ...in the picture A A Visible wall mountings Concealed wall mountings Cabinet assembly gummif dder som leveret ved vandret montage af maskinen skal de leverede gummif dder flyttes til positioner som anvi...

Page 6: ...he condensation drain side The waterseal must be airtight e g by bending a 15 mm copper pipe as a waterseal see the drawing on the left A reinforced water hose is attached between the drain connection...

Page 7: ...even thicker insulation to avoid warm air in the attic from heating the incoming air during the summer Make sure that the closures are tight where the exhaust air duct comes through the roof or throu...

Page 8: ...ated in menu 4 5 User menu and that the setpoint temperature is set in menu 4 8 Service Menu Recommended setpoint is 3 C Reheating of the supply air Since the counterflow heat exchanger cannot recycle...

Page 9: ...ectly mounted with a waterseal and that it is protected from frost Pour 1 litre of water into the condensation container and check that it flows unimpeded through the condensation drain pipe 5 Set all...

Page 10: ...the procedure both knobs must be turned one quarter turn clockwise to the right When the filter has been exchanged or cleaned by shaking them to remove most of the dirt the filter timer is set by pre...

Page 11: ...amage the plates The effect will no longer be optimal if the plates are damaged Fans Remember to switch of the power supply Check the fans in the fan wheel for dirt every third year The four outermost...

Page 12: ...st No incoming air to the residence Error Faulty fan Fouled incoming air filter Fouled outside air grid A fuse has blown on the circuit board No power supply to the facility No exhaust air from the re...

Page 13: ...Belimo Bypass 230VAC H7 R10 Fan extract air 230VAC H8 R12 ON OFF Bypass 2x230VAC H9 R10 Fan supply air 230VAC bypass H16 R8 AUX relay 230VAC max 20W H17 R9 AUX relay 230VAC max 20W 1 1 1 1 1 1 1 1 1 1...

Page 14: ...Brown Brown Blue Blue Yellow green Yellow green Water valve Belimo Bypass Humidity sensor White Red Blue EC fan Supply air Aux relay R8 1x230V 50Hz ONLY control current Red Brown Blue Green Yellow Wh...

Page 15: ...dards hergestellt Directive a Machinery 2006 42 EC 15 March 2006 b Low Voltage 2006 95 EU 12 December 2006 c Electromagnetic Compatibility 2004 108 EC 15 December 2004 d Radio Telecommunication 99 5 E...

Page 16: ...294 71 Benatky nad Jizerou Tel 420 326 373 801 Fax 420 326 373 803 E mail nibe nibe cz www nibe cz PL NL FI DK DE CZ NIBE Energy Systems OY Juurakkotie 3 01510 Vantaa 3C Broom Business Park Bridge Wa...

Reviews: