Menu 5.1.22 - heat pump testing
NOTE
This menu is intended for testing VVM 310 ac-
cording to different standards.
Use of this menu for other reasons may result
in your installation not functioning as intended.
This menu contains several sub-menus, one for each
standard.
Menu 5.1.23 - compressor curve
NOTE
This menu is only displayed if VVM 310 is con-
nected to a heat pump with inverter controlled
compressor.
Set whether the compressor in the heat pump should
work to a particular curve under specific requirements
or if it should work to predefined curves.
You set a curve for a demand (heat, hot water etc.) by
unticking "auto", turning the control knob until a tem-
perature is marked and pressing OK. You can now set at
what temperatures the max. and min. frequencies, re-
spectively will occur.
This menu can consist of several windows (one for each
available demand), use the navigation arrows in the top
left corner to change between the windows.
Menu 5.1.25 - time filter alarm
months btwn filter alarms
Setting range: 1 – 24
Factory setting: 3
Here you set the number of months between alarms for
a reminder to clean the filter in F135
Menu 5.2 - system settings
Make different system settings for your installation here,
e.g. activate the connected heat pump and which ac-
cessories are installed.
Menu 5.2.2 - installed heat pump
If a heat pump is connected to the indoor module, activ-
ate it here.
Menu 5.2.4 - accessories
Set which accessories are installed on the installation
here.
There are two ways of activating connected accessories.
You can either mark the alternative in the list or use the
automatic function "search installed acc.".
search installed acc.
Mark “search installed acc." and press the OK button to
automatically find connected accessories for VVM 310.
Menu 5.3 - accessory settings
The operating settings for accessories that are installed
and activated are made in the sub-menus for this.
Menu 5.3.2 - shunt controlled add. heat
prioritised additional heat
Setting range: on/off
Factory setting: off
start diff additional heat
Setting range: 0 – 2000 DM
Default values: 400 DM
minimum running time
Setting range: 0 – 48 h
Default value: 12 h
min temp.
Setting range: 5 – 90 °C
Default value: 55 °C
mixing valve amplifier
Setting range: 0.1 –10.0
Default value: 1.0
mixing valve step delay
Setting range: 10 – 300 s
Default values: 30 s
Set when the addition is to start, the minimum run time
and the minimum temperature for external addition
with shunt here. External addition with shunt is for ex-
ample a wood/oil/gas/pellet boiler.
You can set shunt valve amplification and shunt valve
waiting time.
Selecting "prioritised additional heat" uses the heat from
the external additional heat instead of the heat pump.
The shunt valve is regulated as long as heat is available,
otherwise the shunt valve is closed.
See the accessory installation instructions for function
description.
NIBE VVM 310
Chapter 8 |
Control - Menus
52
Summary of Contents for VVM 310 EMK
Page 1: ...Installer manual APH NIBE VVM 310 EMK Indoor module IHB EN 1750 8 231175 ...
Page 69: ...Electrical wiring diagram 3x400 V 69 Chapter 12 Technical data NIBE VVM 310 ...
Page 70: ...NIBE VVM 310 Chapter 12 Technical data 70 ...
Page 71: ...71 Chapter 12 Technical data NIBE VVM 310 ...
Page 72: ...NIBE VVM 310 Chapter 12 Technical data 72 ...
Page 73: ...73 Chapter 12 Technical data NIBE VVM 310 ...
Page 76: ......
Page 77: ......
Page 78: ......