Menu 5.3.19 - active cooling 4 pipe
Here you select which pump to use in the system.
Menu 5.3.20 - flow sensor
EMK 500
flow sensor
flow sensor 5.3.20
flow sensor
Setting option: EMK 500, EMK 300 / 310, EMK 150
Factory setting: EMK 500
Here you select which flow sensor is used for the energy
measurement.
Menu 5.3.21 - external energy meter
set mode
Setting range: energy per pulse / pulses per kWh
Default value: energy per pulse
energy per pulse
Setting range: 0 – 10000 Wh
Factory setting: 1000 Wh
pulses per kWh
Setting range: 0 – 10000
Factory setting: 500
The energy meter(s) are used to send pulse signals every
time a certain amount of energy has been consumed.
energy per pulse:
Here you set the amount of energy
each pulse is to correspond to.
pulses per kWh:
Here you set the number of pulses per
kWh that are sent to VVM 310.
Menu 5.4 - soft in/outputs
Here you can select the in/output on the input circuit
board (AA3) the external contact function (page 31) is
to be connected to.
Selectable inputs on terminal block AUX1-5 (AA3-X6:9-
18) and output AA3-X7 (on the input circuit board).
Menu 5.5 - factory setting service
All settings can be reset (including settings available to
the user) to default values here.
NOTE
When resetting, the start guide is displayed the
next time the indoor module is restarted.
Menu 5.6 - forced control
You can force control the different components in the
indoor module and any connected accessories here.
NOTE
Forced control is only intended to be used for
troubleshooting purposes. Using the function
in any other way may cause damage to the
components in your climate system.
Menu 5.7 - start guide
When the indoor module is started for the first time the
start guide starts automatically. Start it manually here.
See page 36 for more information about the start guide.
Menu 5.8 - quick start
It is possible to start the compressor from here.
Caution
There must be a heating or hot water demand
to start the compressor.
Caution
Do not quick start the compressor too many
times over a short period of time as this may
damage the compressor and its surrounding
equipment.
Menu 5.9 - floor drying function
length of period 1 – 7
Setting range: 0 – 30 days
Factory setting, period 1 – 3, 5 – 7: 2 days
Factory setting, period 4: 3 days
temp. period 1 – 7
Setting range: 15 – 70 °C
Default value:
20 °C
temp. period 1
30 °C
temp. period 2
40 °C
temp. period 3
45 C
temp. period 4
40 °C
temp. period 5
30 °C
temp. period 6
20 °C
temp. period 7
55
Chapter 8 |
Control - Menus
NIBE VVM 310
Summary of Contents for VVM 310 EMK
Page 1: ...Installer manual APH NIBE VVM 310 EMK Indoor module IHB EN 1750 8 231175 ...
Page 69: ...Electrical wiring diagram 3x400 V 69 Chapter 12 Technical data NIBE VVM 310 ...
Page 70: ...NIBE VVM 310 Chapter 12 Technical data 70 ...
Page 71: ...71 Chapter 12 Technical data NIBE VVM 310 ...
Page 72: ...NIBE VVM 310 Chapter 12 Technical data 72 ...
Page 73: ...73 Chapter 12 Technical data NIBE VVM 310 ...
Page 76: ......
Page 77: ......
Page 78: ......