background image

EN

16

– English

7.4.2 - Flashing light signals

If a flashing light is connected to the FLASH output on the control unit (or the
LED flashing light is used, optional accessory), during the performance of a
manoeuvre this emits a flash each second. If faults occur, the flashing light will

emit shorter flashes; these are repeated twice, separated by a 1 second pause.
The same signals are also emitted by the LED flashing light (optional accesso-
ry) and the “Bluebus” LED. Table 

14

shows the cause and solution for each

type of signal.

7.5 - Loop Detector

The control unit has two circuits used to detect metal masses (motorcycles,
cars, trucks, etc…); each circuit may be completed with the use of a inductive
loop, consisting of 1 unipolar cable, to be positioned below the ground at a
depth of a few centimeters.

7.5.1 - Operation

When the control unit detects a variation in frequency with the passage of a
metal mass above the loop, it activates a manoeuvre or an output (output 1, 2,
3) to activate the flashing light, the open barrier indicator or the lights for the
pole. The factory setting controls an opening manoeuvre of the pole; until the
loop is operating, it is not possible to control the closing manoeuvre.
When the control unit is powered, it carries out a calibration, i.e. a measure-
ment of the operating frequency of each loop; if no loop is connected to the
control unit, the circuit automatically turns off after 30 seconds.
There are 8 levels of “metal mass detection sensitivity” (see Table 7 chapter 6).
The factory setting is 90%.
By using the Oview programmer, it is possible to modify the other parameters
and operating modes associated to the Loop Detector.
The following programs are possible, also see 

Table 15

for the values:

• Loop sensitivity:

set the minimum frequency variation of the metal mass,

required to activate the manoeuvre. Reference parameters:
- set a “high sensitivity” for the detection of small sized metal masses
- set a “low sensitivity” for the detection of large sized metal masses.

• Loop power supply:

activates or deactivates the circuits of the loop detec-

tor.

• Activate loop 1, 2:

the activation of the loop makes the movement of the

barrier activate according to the set operating mode. If the function is DEAC-
TIVATED, the status of the loop is available, by suitably programming one of
the outputs (output 1, 2, 3) on the control unit, with the Oview programmer.

• Loop permanence time:

time during which the loop is occupied. Once this

time has passed, a recalibration is automatically activated to signal the free
loop.

• Loop operation mode:

if the function “Loop active” is enabled and the loop

command signal is ACTIVE, the behaviour of the barrier varies according to

the set “loop operation mode”:
- only opens (apartment block opens)
- only closes
- alt
- photo closes (PHOTO with total inversion)

• Calibration:

starts a calibration procedure; i.e. acknowledgement of the con-

nected loop. Note: the calibration automatically activates the parameter
“Loop power supply”

• Activation modes: 

see 

Table 16

(relay = loop command signal).

• Loop activation time:

is the time “

t

” linked to the operating modes

described in 

Table 16

.

• Loop frequency display:

signals the fluctuation frequency of the loop

selected in Hz.

7.5.2 - Installation

WARNINGS

• It is advisable to install the magnetic loop near the barrier.
• The electric cables of the magnetic loops must be separated from the other

cables in the barrier (power supply, accessories, etc.).

• If the magnetic loops are connected to other barriers, it is necessary to posi-

tion them at least 1 m between each other.

Important!

– The magnetic loop must be fixed in a way to make it immobile

since any movement caused by an unstable floor could cause false tripping.

• The size of the loop must be defined depending on the application; it is nec-

essary to consider that the loop must be positioned at a distance of at least
20 cm from fixed metal objects and 1 m from moving metal objects (

fig. F

).

Note – To obtain optimal operation, it is worth using a loop that is the same
size as or smaller than the object to be detected.

• Usually the loop used for the passage of cars and trucks is rectangular in

shape, to be positioned 45° with respect to the route arranged for the pas-
sage of bicycles and motorbikes (

fig. G

). 

Note – We recommend you cut the

45° corners of the outline on the floor to avoid breaking the cable.

IMPORTANT

– TO PREVENT INTERFERENCE, 

THE CONNECTION CA -

BLES OF THE LOOP MUST BE TWISTED AT LEAST 20 TIMES A
METER AND THERE MUST BE NO JOINTS

. Should it be necessary to

extend the cable, weld the conductors and seal them with the thermo-shrink-

TABLE 14

Signal

Cause

Solution 

1 flash
second pause
1 flash

Bluebus system error

At the start of the manoeuvre, the devices connected to Bluebus
do not correspond to those recognized during the self-learning
phase. One or more devices may be faulty; check and, if necessa-
ry, replace them. In case of modifications repeat the device self-
learning process (see paragraph 4.5).

2 flashes
second pause
2 flashes

Photocell activated

At the start of the manoeuvre, one or more photocells do not ena-
ble it; check to see if there are any obstacles.

3 flashes
second pause
3 flashes

Activation of Motor Force limiter

During the movement, the pole has experienced excessive fric-
tion; identify the cause.

6 flashes
second pause
6 flashes

Not used

7 flashes
second pause
7 flashes

Error in internal electric circuits

Disconnect all power circuits for a few seconds and then retry a
command; if the condition persists this may indicate a serious
fault with the board or motor wiring. Check and make replace-
ments as necessary.

8 flashes
second pause
8 flashes

Not used

9 flashes
second pause
9 flashes

Block automation

Send the command “Release automation” or control the manoeu-
vre with “High Priority Step Step”.

4 flashes
second pause
4 flashes

STOP input activation

At the start of the manoeuvre or during the movement, the STOP
input was activated; identify the cause.

5 flashes
second pause
5 flashes

Error on internal parameters in control unit

Switch off the power and turn it on again. If the error continues car-
ry out the “Total deletion of the memory” as described in chapter 7.1
and redo the installation; if the condition persists, there may be a
serious malfunction and the electronic board must be replaced.

Summary of Contents for M3BAR

Page 1: ...ctions et avertissements pour l installation et l utilisation ES Instrucciones y advertencias para la instalaci n y el uso DE Installierungs und Gebrauchsanleitungen und Hinweise PL Instrukcje i ostrz...

Page 2: ......

Page 3: ...ngs On the power line to the system install a device for disconnection from the power mains with a gap between contacts that assures complete discon nection in the conditions of overvoltage category I...

Page 4: ...e S p a product catalogue The electromagnetic compatibility may not be guaranteed if the product is used in configurations or with other products that have not been foreseen the use of the product is...

Page 5: ...riers for residential and indus trial use they control the opening and closing of a road transit point with widths from 3 to 8 metres IMPORTANT All uses other than the intended use described and use i...

Page 6: ...aracteristics of electrical cables 3 3 1 Modifying the factory settings of the Closure manoeuvre If Closure to the right is required proceed as follows MBAR Version 01 Remove the cover fig 4 02 Loosen...

Page 7: ...ncy must be checked and ensure that the 4 anchoring points can resist a load of at least 1000 Kg For fixture use 12 MA screws 3 5 Pole installation 3 5 1 Pole support assembly 01 Insert the two plugs...

Page 8: ...fig 24 03 Insert the universal joint in the free ends of the two poles Take care in cor rectly directing the joint since the heads of the screws must be on the same part of the holes on the poles fig...

Page 9: ...output In the factory it is configured for operation with Pole Open Indicator 24 V 10 W BLUEBUS this terminal enables the connection of compatible devices all are connected in parallel with just two...

Page 10: ...rom the power mains and insert the receiver as shown in fig 42 Table 5 shows the actions performed by the control unit according to the out puts activated or the commands sent from the radio receiver...

Page 11: ...ing the optic axis joining the two photocells by means of a cylin der diameter 5 cm length 30 cm Fig C pass the cylinder first close to the TX photocell then close to the RX and lastly at the centre b...

Page 12: ...n Paragraph 4 5 EN 10 English The control unit has 3 keys OPEN STOP Set CLOSE Fig 49 that can be used both for controlling the unit during testing and for programming the available functions The progr...

Page 13: ...the type of voltage of the selected programming level 1LIGHT Output WARNINGS Do not set an excessively high value for the motor force as this may impair operation of the safety system or damage the p...

Page 14: ...he Set key for approx 3 seconds 02 Release the key when LED L1 starts flashing 03 Press the key or to move from the LED that is flashing to LED L4 LIGHT output input LED 04 Press and hold the Set key...

Page 15: ...ction opens FA1 and opens FA2 can be connected to the Bluebus input it is necessary to cut the A jumper at the rear of TX and RX cards When these photocells intervene the control unit commands an open...

Page 16: ...olution Off All OK CLOSE input not active On CLOSE input activation Normal if the device connected to the CLOSE input is active FC1 limit switch LED Cause Solution Off Limit switch activation If the p...

Page 17: ...n During normal operation indicates Stand BY active Flashes Programming of functions in progress If this flashes together with L3 this indicates that the device learning phase of the opening and closi...

Page 18: ...Loop activation time is the time t linked to the operating modes described in Table 16 Loop frequency display signals the fluctuation frequency of the loop selected in Hz 7 5 2 Installation WARNINGS...

Page 19: ...maximum temperature admitted for the isola tion of the cable otherwise a loss in isolation towards the earth may occur TABLE 15 Function Values Default Loop 1 sensitivity 10 100 90 Loop 2 sensitivity...

Page 20: ...it is possible to carry out the following connections its own flashing light Flash its own Pole Open Indicator S C A pole lights its own sensitive edge Stop its own command device P P which commands t...

Page 21: ...he event of illegal dis posal of this product The manoeuvre is performed but shortly afterwards the pole blocks or performs a brief inversion the selected force value may be too low to enable the move...

Page 22: ...output for signal indicator 24V max 10W Output for flashing light with optional accessories XBA7 LED flashing light or XBA8 LED traffic light traffic light on cover BLUEBUS output 1 output with maxim...

Page 23: ...cil of 21 December 1988 regarding the approximation of legislation regulations and administration of Member States concerning construction products according to the following harmonised standards EN 1...

Page 24: ...02 Radio spectrum art 3 2 EN 300 330 2 V1 5 1 2010 In accordance with directive 1999 5 CE annex V the product is classified as class 1 and marked DIRECTIVE 2004 108 EC OF THE EUROPEAN PARLIAMENT AND C...

Page 25: ...sh es and the manoeuvre is not started the number of flashes depends on the reason for which the manoeuvre does not start In this case the user must press and hold the command within three seconds Aft...

Page 26: ......

Page 27: ...he test procedure 10 Check protection against the risk of lifting on automations with vertical movement it must be ensured that there is no risk of lifting This test can be performed as follows hang a...

Page 28: ...lish Date Description of operation describe checks adjustments repairs modifications etc Signature of technician Signature of owner That all phases as envisaged in the maintenance schedule have been p...

Page 29: ...mm 464 5 mm 400 mm 1219 5 mm 900 mm M3BAR M5BAR M7BAR L Bar 298 5 mm 464 5 mm 500 mm 1219 5 mm 900 mm EN with joint IT con giunto FR avec raccord ES con uni n DE mit Gelenkverbindung PL ze z czk NL m...

Page 30: ...II 4 3 b a c d g h f e c a b...

Page 31: ...III 5 6 MBAR a c d b...

Page 32: ...IV 90 8 9 MBAR a b c a b 7 a b...

Page 33: ...V 180 10 11 LBAR c a a b...

Page 34: ...VI 13 14 12 LBAR c a b...

Page 35: ...VII 15 16 18 17...

Page 36: ...VIII 19 20 21 23 22...

Page 37: ...IX 24 26 25 28 1 cm 27 29...

Page 38: ...X 33 34 30 31 32 c a b c a b...

Page 39: ...XI 35 36 37 45 38 a b a b c...

Page 40: ...C NO NO C C MOTB MOFB OPEN CLOSE TX RX 24V 4W LIGHT FLASH SCA BLUEBUS STOP OPEN CLOSE P P LIGHT FLASH SCA BLUEBUS STOP OPEN CLOSE P P LOOP2 LOOP1 41 IN 1 IN 2 IN 3 LOOP 2 MASTER SLAVE LOOP 1 OUT 3 OUT...

Page 41: ...XIII 42 43 44 STOP 45 46 LIGHT 47...

Page 42: ...XIV 48 49 50 a b c...

Page 43: ...XV 51 52 a b...

Page 44: ...XVI 53 a b c d e f g...

Page 45: ...FLASH SCA MOTB OPEN CLOSE TX RX BLUEBUS STOP OPEN CLOSE P P 24V 4W BUS T4 M S LOOP2 LOOP1 LIGHT FLASH SCA BLUEBUS STOP OPEN CLOSE P P 24V 4W BUS T4 M S LOOP2 LOOP1 NC NC NO NO C C NC NC NO NO C C 54 M...

Page 46: ...XVIII F1 F1 F2 F2 55...

Page 47: ......

Page 48: ...ISTML BARR01 4865_07 10 2011 www niceforyou com Nice SpA Oderzo TV Italia info niceforyou com...

Reviews: