background image

22 

– ENGLISH

FURTHER INFORMATION 

(Accessories)

9

 

FURTHER DETAILS (Accessories)

9.1  ADDING OR REMOVING DEVICES

Once the automation has been assembled, it is possible to add 

or remove devices at any time. In particular, various types of de-

vices can be connected to the “

BlueBUS

” and “

STOP

” inputs, 

as described in the following paragraphs.

After having added or removed devices, these must 

be learned as described in the “Learning of other 

devices” paragraph.

9.1.1 BlueBUS

BlueBUS is a technique that allows for connecting compatible 

devices with only two wires which carry the electrical power and 

the communication signals. All devices are connected in paral-

lel on the same 2 BlueBUS wires and without having to observe 

the polarities; each device is recognised because it is assigned 

a univocal address during the installation phase.

The following devices can be connected to the BlueBUS: photo-

cells, safety devices, control buttons, signalling lights, etc. The 

control unit recognises all the connected devices individually 

through an appropriate learning phase, and can detect all pos-

sible anomalies with absolute precision.

For this reason, whenever a device is connected to or removed 

from BlueBUS, the learning phase must be carried out on the 

control unit, as described in the “

Learning of other devices

” 

paragraph.

9.1.2 STOP input

STOP is the input that causes immediate stoppage of the ma-

noeuvre followed by its brief reversal. Devices with output fea-

turing normally open “NO” and normally closed “NC” contacts, 

as  well  as  devices  with  8.2  kΩ  fixed  resistor  output,  such  as 

sensitive edges, can be connected to this input.

As with the BlueBUS, the control unit recognises the type of 

device connected to the STOP input during the learning phase 

(see the “

Learning of other devices

” paragraph); subsequent-

ly the control unit gives a STOP command when it detects a 

variation with respect to the recognised status.

Multiple devices, even of different types, can be connected to 

the STOP input if suitable arrangements are made:

 

Any number of NO devices can be connected to each other 

in parallel.

 

Any number of NC devices can be connected to each other 

in series.

 

Two devices with 8.2 kΩ fixed resistor output can be connect-

ed in parallel; if there are more than 2 devices then they must 

all be connected in cascade, with a single 8.2 kΩ terminating 

resistor.

 

It is possible to combine two NO and NC contacts by placing 

them in parallel, while also mounting a 8.2 kΩ resistor in series 

with the NC contact (this also allows for combining 3 devices: 

NA, NC and 8.2 kΩ).

If the STOP input is used to connect devices with 

safety  functions,  only  those  devices  with  8.2  kΩ 

fixed resistor guarantee Category 3 safety against 

faults in accordance with the EN 13849-1 standard.

9.1.3 Photocells

To allow the control unit to recognise the devices connected 

through  the  “BlueBUS”  system,  these  devices  must  be  ad-

dressed.

This operation can be carried out by correctly positioning the 

electrical jumper present in each device (also refer to the in-

struction manual of each device). Shown below is an address-

ing diagram for photocells, based on their type.

FOTO 1

FOTO

FOTO II

FOTO 1 II

FOTO 2 II

FOTO 2

40

Table 10

PHOTOCELL ADDRESSES

Photocell

Position of the 

jumpers

FOTO (PHOTO)

External photocell h = 50 activated during 

the closing phase (stops and reverses the 

gate’s movement)

FOTO II (PHOTO II)

External photocell h = 100 activated 

during the closing phase (stops and 

reverses the gate’s movement)

FOTO 1 (PHOTO 1)

Internal photocell h = 50 cm with 

activation both during closing (stops 

and reverses the movement) and during 

opening (stops and restarts when the 

photocell disengages)

FOTO 1 II (PHOTO 1 II)

Internal photocell h = 100 cm with 

activation both during closing (stops 

and reverses the movement) and during 

opening (stops and restarts when the 

photocell disengages)

FOTO 2 (PHOTO 2)

Internal photocell triggered during the 

opening phase (stops and reverses the 

gate’s movement)

FOTO 2 II (PHOTO 2 II)

Internal photocell triggered during the 

opening phase (stops and reverses the 

gate’s movement)
FOTO 3 (PHOTO 3)

CONFIGURATION NOT ALLOWED

At the end of the installation procedure, or after 

photocells or other devices have been removed, the 

learning procedure must be carried out (see para-

graph “Device learning“).

Summary of Contents for PP7124

Page 1: ...Nice PP7124 Swing gate opener EN Instructions and warnings for installation and use...

Page 2: ...ion process handle the product with care by avoiding crushing impacts falls or contact with liquids of any kind Do not place the product near sources of heat nor expose it to open flames All these act...

Page 3: ...ontrolled by a fire sensing system make sure that any windows larger than 200 mm are closed using the control elements Prevent and avoid any form of entrapment between the moving and fixed parts durin...

Page 4: ...iquids keep the product away from heat sources and open flames and acid saline or potentially explosive atmospheres these may damage the product and cause malfunctions or danger ous situations if ther...

Page 5: ...t s actual useful life Example of lifetime calculation automation of a gate with a 1 3 m long leaf weighing 180 kg for example with a solid leaf Table 1 shows the severity indices for this type of ins...

Page 6: ...ommended 5 m 4 BLUEBUS DEVICES cable 1 cable 2 x 0 5 mm2 Maximum length 20 m note 2 5 KEY SELECTOR cable 2 cables 2 x 0 5 mm2 note 3 Maximum length 50 m 6 ELECTRIC LOCK cable 1 cable 2 x 1 mm2 Maximum...

Page 7: ...resulting opening angle 3 with the value of distance A and the opening angle found using the graph to determine the distance B For example if A is 100 mm and the desired angle is equal to 100 distanc...

Page 8: ...racket for the gate leaf I to the curved arm F D H F I G G H 15 10 unlock the gearmotor manually see paragraph Manually unlocking and locking the gearmotor 11 decide where to attach the bracket to the...

Page 9: ...mit switch A as shown in the figure 4 loosen the screw that fastens the straight arm to the gear motor 5 apply the protective cover B and re tighten the screw with the washer A B 19 6 move the gate to...

Page 10: ...nection under the Category III overvoltage conditions in accordance with the installation instructions To make the electrical connections 1 open the gearmotor s cover A A 21 2 pass the power cable and...

Page 11: ...Example EPM EDSB ETPB For further information on the BlueBUS refer to the BlueBUS paragraph Stop Input for devices that suspend or even stop the current manoeuvre Normally Closed and Normally Open co...

Page 12: ...EBUS L1 L2 26 The learning process of connected devices can be repeated at any time even after the installation for example whenever a device must be added to complete the new learning process refer t...

Page 13: ...signal the current position STOP SBS OPEN BLUEBUS L1 29 To effect the manual learning procedure 1 simultaneously press and hold the and g buttons h 2 release the buttons when LED L1 starts flashing af...

Page 14: ...on to be programmed 5 proceed for each individual position as described in the Learning in manual mode paragraph 6 repeat this last operation for all the other positions to be modified 5 4 CHECKING TH...

Page 15: ...impact force it is neces sary to test various adjustments to find the one that gives the best results 6 2 COMMISSIONING a Commissioning can only be performed after all test ing phases have been succe...

Page 16: ...ing will not take place if the function is disabled L3 Always Close Function ENABLED in the event of a blackout even of short duration if the control unit detects that the gate is not closed once the...

Page 17: ...omatic Closing is enabled L2 15 seconds L3 30 seconds L4 45 seconds L5 60 seconds L6 80 seconds L7 120 seconds L8 180 seconds L2 Step by Step function L1 Open Stop Close Stop Controls the sequence of...

Page 18: ...d M2 opens to 110 the minimum opening is 90 L2 Pedestrian 2 the M2 gate leaf opens to 1 2 of the full range L3 Pedestrian 3 the M2 gate leaf opens to 3 4 of the full range L4 Pedestrian 4 full opening...

Page 19: ...he limit Lit for 2 seconds at the start of the opening manoeuvre Between 81 and 100 of the limit Flashes for the entire duration of the manoeuvre Exceeding 100 of the limit Flashes always 7 4 3 Verify...

Page 20: ...uring the learning phase There may be defective devices check and replace them if necessary if changes have been made the learning procedure must be repeated 2 flashes 1 second pause 2 flashes Interve...

Page 21: ...r to that shown in Table 8 STOP LED OFF Intervention of the STOP input Check the devices connected to the STOP input On Everything normal STOP input active Sbs LED OFF Everything normal Sbs input not...

Page 22: ...ices can be connected to each other in parallel Any number of NC devices can be connected to each other in series Two devices with 8 2 k fixed resistor output can be connect ed in parallel if there ar...

Page 23: ...commands shown in Table 12 Table 12 OXI IN EXTENDED MODE II No Command Description 1 Step by Step SbS Step by Step command 2 Partial opening 1 Partial opening 1 command 3 Open Open command 4 Close Cl...

Page 24: ...p the spring G by its two ends 6 thread the other end of the cable through the hole located on the lower part of the gearmotor 7 put the cover back on A A C B G D E F 44 8 connect the cable to Kio by...

Page 25: ...B in the appropriate slot C on the control unit s electronic board 3 insert the cable D in the appropriate slot E on the in terface C B D E A 45 4 At this stage the control unit can be powered again l...

Page 26: ...ST NOT BE POWERED by the elec tricity grid at the same time l For information on the Solemyo system consult the relevant instruction manual To connect the Solemyo system 1 remove the cover A 2 remove...

Page 27: ...components replace any worn parts 5 connect the power supplies again and run all the tests and checks described in the Testing paragraph PRODUCT DISPOSAL 11 11 PRODUCT DISPOSAL l This product is an in...

Page 28: ...que 10 minutes Application limits The product can be used on gates with leaves weighing up to 200 kg for lengths up to 2 m Durability Estimated between 80 000 and 250 000 cycles depending on the condi...

Page 29: ...cated fixing plate Operating temperature 20 C 55 C at low temperatures the gearmotor s efficiency decreases Use in highly acid saline or potentially explosive atmosphere No Protection rating IP 44 wit...

Page 30: ...lowing directives according to the requirements envisaged for partly completed machinery Annex II part 1 section B Directive 2006 42 EC of the EUROPEAN PARLIAMENT AND COUNCIL of 17 May 2006 related to...

Page 31: ...ENGLISH 31 NOTES...

Page 32: ...32 ENGLISH NOTES...

Page 33: ...uipped with back up batteries the automation can none theless be used by manually unlocking the motor consult the instructions at the end of the chapter and moving the gate leaf manually Safety device...

Page 34: ...has come to a standstill To unlock the device 1 raise the small cover 2 insert the key A and turn it clockwise by 90 A 48 3 the gate leaf can now be moved manually to the desired position To lock the...

Page 35: ...ENGLISH 35 NOTES...

Page 36: ...www niceforyou com Nice SpA Via Callalta 1 31046 Oderzo TV Italy info niceforyou com IDV0668A00EN_31 01 2019...

Reviews: