24
– ENGLISH
9.3 CONNECTING AND INSTALLING THE BACK-
UP BATTERY
f
The electrical connection of the battery to the con-
trol unit must be made only after completing all the
installation and programming stages, as the battery
is an emergency power supply.
To install and connect the battery:
1.
remove the cover (
A
)
2.
slide the battery (
B
) into its housing
3.
remove the plastic protection (
C
) with the aid of a screw-
driver
4.
insert the relative connector (
D
) on the control unit.
A
B
D
C
43
9.4 CONNECTING THE EXTERNAL UNLOCKING
SYSTEM KIO
a
Kio must be connected to the gearmotor that drives
the leaf that starts moving first (when the gate is
closed).
For the connection, proceed as follows:
1.
remove the lower plastic cover (
A
)
2.
insert the pin (
C
) through the hole of the release shaft (
C
)
3.
insert the steel cable (
D
) first through the pin (
F
), then
through the appropriate hole (
E
) and through the pin hole
(
C
)
4.
lock the cable in place by tightening the pin (
F
)
5.
hook up the spring (
G
) by its two ends
6.
thread the other end of the cable through the hole located
on the lower part of the gearmotor
7.
put the cover back on (
A
)
A
C
B
G
D
E
F
44
8.
connect the cable to Kio, by referring to the respective
instruction manual.
9.5 CONNECTING THE OVIEW PROGRAMMER
The “
Oview
” programming unit can be connected to the control
unit.
This unit allows for rapidly and fully programming the functions,
adjusting the parameters, updating the control unit firmware,
running the diagnostics to detect any malfunctions and perform-
ing routine maintenance.
The “
Oview
” allows for operating on the control unit at a maxi-
mum distance of roughly 100 m. If several control units are net-
worked with each other in a “BusT4” network, by connecting the
“
Oview
” to one of these units, it is possible to view on the dis-
play all the networked control units (up to a maximum 16 units).
The “
Oview
” unit can also be left connected to the control unit
during normal operation of the automation, so that the user can
send commands using a specific menu.
a
Before connecting the IBT4N interface, it is neces-
sary to disconnect the control unit from the power
supply.