EN
10
– English
Possible causes of malfunctions are listed below, which may occur during the
installation phase, or in the case of faults, possible remedies:
• The radio transmitter does not control the barrier and the transmitter led
does not illuminate:
Check that the transmitter batteries are not discharged
and replace if necessary.
• The radio transmitter does not control the barrier but the transmitter led illu-
minates: check that the transmitter is correctly memorised on the radio receiv-
er. Ensure correct emission of the radio signal of the transmitter with the follow-
ing empirical test: Press a key and place the led against the aerial of a standard
radio switched on and tuned to FM at the frequency of 108.5Mhz or as close to
this value as possible; a slight noise with a scratching pulse noise should be
heard.
• No manoeuvre is performed when a command is sent, and the OK led
does not flash:
check that the barrier is powered via the mains at 230 V. Also
check that the fuses F1 and F2 are not blown; in this case try to locate the
cause of the fault and then replace with a version with the same specifications;
see
fig. 42
.
• No manoeuvre is performed when a command is sent, and the flashing
light remains off:
check that the command is effectively received; if the sent
command reaches the SS input, the OK led emits a double flash to indicate that
the command is received.
• The manoeuvre does not start and the courtesy light flashes a few ti -
mes:
count the number of flashes and check with reference to the data in
Table
9
in Chapter 8.
• The manoeuvre is performed, but shortly afterwards the pole blocks and per-
forms a brief inversion: the selected force value may be too low to enable
movement of the pole. Check correct balancing of the pole; if necessary set a
higher force value.
WHAT TO DO IF…
(troubleshooting guide)
7
8.1 - Total deletion of control unit memory
It is possible to delete all memorised data on the control unit and reset it to the
original factory settings:
01.
Press and hold down “
▲
“ and “
▼
“ keys at the same time;
02.
Release the keys when all Led illuminate (after approx.3 seconds);
03.
When leds
L1
and
L2
start flashing, this means that the procedure is ter-
minated.
Important
– This procedure does not delete the parameter regarding the direc-
tion of motor rotation and the number of manoeuvres performed.
8.2 - Other functions
• “Always open” function
This function is a special feature of the control unit; it is associated with the
“Step Step” input and enables an “always open” command when the Step Step
command remains active for more than 3 seconds. This function is valid for any
setting of the Step Step input (see “SS Function” in
Table 7
).
For example, it can be used to connect a clock for programming permanent
opening of the barrier during a specific time band.
• “Move anyway” function
If one or more safety devices malfunctions or is out of service, this function
enables control of the barrier in “hold-to-run” mode (for details, see chapter
“operation manual”).
• “Maintenance notification” function
This function enables notification of when an automation maintenance check is
necessary. The “Maintenance notification” parameter can be set with a value on
8 different levels (see
Table 7
).
The levels refer to the number of manoeuvres performed. The maintenance
notification is signalled via the Flash flashing light or by the maintenance indica-
tor according to the type of setting. The signals emitted by the Flash flashing
light and the maintenance indicator are shown in
Table 9
.
• Check of number of manoeuvres performed
The function “Maintenance notification” enables the user to check the number
of manoeuvres performed as a percentage of the maximum set limit. Proceed
as shown in
Table 10
.
• Manoeuvre counter reset
The manoeuvres can be reset at the end of the automation maintenance
phase. To proceed, see
Table 11
.
FURTHER DETAILS
8
TABLE 9
Number of manoeuvres
Flash flashing light
Maintenance indicator
Below 80% of the limit
Normal (0.5 sec. lit - 0.5 sec. off)
Light on for 2 seconds at the start of the
opening manoeuvre.
Between 81% and 100% of the limit
Light on for 2 seconds at the start of the manoeuvre.
Flashing for entire duration of manoeuvre then
continuing as normal
Over 100% of the limit
At the start and end of the manoeuvre, remains lit
Always flashes
for 2 sec., then continues as normal.
TABLE 8
-
Programming procedure (second level functions)
01.
Press and hold down the “
Set
” key for approx. 3 seconds;
02.
Release the key when LED
L1
starts flashing;
03.
Press keys “
▲
” or “
▼
” to move from the flashing led to the led associated with the function to be modified;
04.
Press and hold the “
Set
” key through to completion of point 06;
05.
Wait approx. 3 seconds, until the LED representing the current level of the parameter to be modified illuminates;
06.
Press keys
▲
or
▼
to move the LED representing the value of the parameter;
07.
Release the “
Set
” key;
08.
Wait 10 seconds (maximum time) to exit the programming mode.
Note
– During this procedure, points 03 to 07 need to be repeated when programming other parameters during the phase itself.
SET
SET
SET
SET
L1
or
or
3 s
10 s
Summary of Contents for S-BAR
Page 78: ...I 2 1 A B C B 179 5 mm 330 mm 1146 mm 826 mm 4000 mm 3 b a d e f g h c ...
Page 79: ...II 5 A B C 1 2 4 ...
Page 80: ...III 9 10 90 6 A C B 7 8 B A ...
Page 81: ...IV 14 15 A B A B 11 A B 12 13 A B ...
Page 82: ...V 16 A B 17 18 ...
Page 83: ...VI 20 180 21 C C A B 1cm 1cm 19 A C B ...
Page 84: ...VII 22 23 26 L N 24 1 2 25 ...
Page 86: ...IX 30 A A B STOP 31 A B ...
Page 87: ...X 32 A B C D STOP 33 A B 34 ...
Page 88: ...XI 35 36 L8 37 A B 2 1 L7 L8 L8 A B C Op L5 L6 L7 L8 Stop Set Close F u s e 1 A T 38 ...
Page 89: ...XII 300 200 700 500 39 300 200 700 500 150 40 41 ...
Page 90: ...a c d e b XIII F2 F1 42 43 ...
Page 91: ...XIV 44 O pe n L1 L2 L3 L4 L5 L6 L7 L8 St op Se t Cl os e Fuse 1AT 45 f g ...
Page 93: ...IST SBARR01 4865_20 10 2011 www niceforyou com Nice SpA Oderzo TV Italia info niceforyou com ...