9.6.3 Connection details
In this paragraph are explained the feature and the possible connection of the control board.
The control board terminals are opto-insulated.
The available features can be different depending on the fan model.
Without using the STOP switch
Using the STOP switch
Do not reverse the input signal or connect the +10V, 12V or +24V to signal ground. The driver could be
damaged. Do not apply signals with voltage outside the indicated limits, the driver could be damaged.
WARNING
WARNING
9.6.3.1 Analog
This is the driver default mode and the signal must be connected into the ANALOG INPUT and the reference
to GND.
The analog input can accept also a PWM signal with f>1kHz.
With 3-phase drivers, a jumper or a switch is needed between 10 or 24 V and Enable to start the fan. See also
paragraphs 9.6.3.3 and 13.3.
WARNING
WARNING
Do not use devices having the signal
GND connected to the NEUTRAL ca-
ble of the power supply. The driver
may be damaged or not functioning
properly.
The ava10V power supply of
the driver is intended to be used with
a potentiometer of minimum 2KOhm,
with a max absorbed current of 5mA.
Any different devices connected to it
could bring to an undesired functioning
of the driver or of connected device.
Nicotra Gebhardt
can provide a ded-
icated potentiometer: REGPOT code
K43138.