Holding Register 2: Max Speed [RPM]
This register can be used to set the max speed of the fan.
Allowed values = [Min Speed, Default Value]
Default value = table below
280
315
355
400
450
500
560
630
1.05kW 1-Phase
2600 2200 1800
-
-
-
-
-
2.1kW
1-Phase
3200 2770 2080 1700
-
-
-
-
2.65kW 3-Phase
3700 3100 2500 2000
-
-
-
-
5.5kW
3-Phase
-
-
2860 2380 1910 1650 1260 1000
Holding Register 7: Max Current [mA]
This register can be used to reduce the max motor current.
Allowed values = [1, Default value]
Default value = table below
280
315
355
400
450
500
560
630
1.05kW 1-Phase
5000 6000 5000
-
-
-
-
-
2.1kW
1-Phase
7220 6700 7600 7000
-
-
-
-
2.65kW 3-Phase
8000 8000 8000 7200
-
-
-
-
5.5kW
3-Phase
-
-
11000 13300 12700 12000 11000 10500
Although the value of the Max Current can be set at any value being lower than the original default
one, it is not recommended using a value that is 0.3 times below the default one.
17.3.3 Holding Register 2
17.3.4 Holding Register 7
17.3.5 Holding Register 16
Holding Register 16: Speed Threshold Low [RPM]
This register can be used to set the speed threshold low.
The register is active when the
register 46 is set to the value 3.
355
400
450
500
560
630
5.5kW
3-Ph.
2300 1800 1300 1100
900 20000
17.3.6 Holding Register 21
Holding Register 21: Fixed Speed setting [RPM]
This register can be used to set the speed in
Fixed Speed Control Mode.
The register is active when the Input Type
Holding Register 34 is set to the value 2.
Allowed values = [Min Speed, Max Speed]
Default value = 0