Holding Register 47: Modbus Speed [10−1 kbps]
This register can be used to set the Modbus speed.
Allowed values = table on the following page
Default value = 96
96
corresponding to 9.6kbps
192
corresponding to 19.2kbps
384
corresponding to 38.4kbps (not available using the RS485 port)
576
corresponding to 57.6kbps (not available using the RS485 port)
Holding Register 48: Modbus Stop Bits [Adim] (Default = 0)
This register can be used to set the parity and the stop bits.
Allowed values = table below
Default value = 0
0 2 Stop Bits/No Parity
1 1 Stop Bit/Even Parity
2 1 Stop Bit/Odd Parity
Holding Register 50: External Set [10−1 V]
This register can be used to set the reference of the PID control.
Allowed values = [0, 100]
Default value = 0
The register is active when the Input Type Holding Register is set to the value 12.
Holding Register 51: Kp [Adim]
This register can be used to set the Proportional Gain of the PID control.
Allowed values = [0, 32767]
Default value = 0
Holding Register 52: Ki [Adim]
This register can be used to set the Integral Gain of the PID control.
Allowed values = [0, 32767]
Default value = 0