background image

4(8)

Servodan A/S | Tel +45 7442 4726 | Fax + 45 7442 4035 | info@servodan.dk | www.servodan.com

41Y773_03_R1_131104CWH

GB

User manual

Motion detector 8 m high ceiling,  
slave, 41-773

Use

The motion detector 360° slave is used together with  
41-771, for widening the detection range. 

Function

It is possible to connect 10 slave detectors (41-773) to one  

41-771 (master) which will control the load with its settings.

Master and slave motion detectors have the same range.

To achieve complete coverage by using several detectors, 

it is recommended that an overlap of approximately 30% is 

calculated. 

Fig. 1.

Installation

Location:
The detector responds to movement and heat in relation to the 
surroundings. Avoid placing the detector close to heat sources 
such as ventilation systems, or moving objects. This may 
cause unwanted activation. If installed in warehouses where 

closed trucks are used, reduced functionality may occur due to 
differences in temperature being so slight. 

Fig. 2.

 

Range:
The recommended installation height for this detector is 4-8 m. 
At this height the detector has a range of Ø 16-32 m (without the 
lens cover). 

Fig. 3.

Installation:
The detector is designed for mounting on the ceiling. 

Fig. 4.

Connection:
The detector must only be connected to a power supply once all 
wire connections have been connected.

After connection to the power supply, the detector will be ready 
to operate after approximately 40 seconds (warm-up time). The 
red LED flashes for 0.25 seconds on and for 2 seconds off during 
warm-up. The end of the warm-up time is indicated with two 
short flashes from the green LED. 

For wiring diagram, 

Fig. 5.

Setting

Factory settings: 

Fig. 6

Sensitivity: High sensitivity

DIP Sensitivity setting: 

 

Off  Off  Minimum sensitivity

 

Off  On   Low sensitivity

 

On  Off  High sensitivity

 

On  On  Maximum sensitivity

 
Walk-test:
A walk-test can be carried out to check that the detector is 
detecting correctly.

Select walk-test via the Time potentiometer (minimum position). 

Fig. 7

When the walk-test is activated, the blue LED switches on, 
and when the detector detects movement, the red LED and 
connected lighting will switch on for five seconds. The blue LED 
is inactive when the connected lighting is on. 

NB! The walk-test is daylight

-independent

.

Setting via potentiometers:
The potentiometer has one function: Test

In order to activate the test, turn the potentiometer to the 
minimum position. After the test has been completed, return the 
potentiometer to the medium position. 

Operation & maintenance

Dirt affects the operation of the detector and the detector’s lens 

must therefore be kept clean. Use a damp cloth for cleaning. Use 

water mixed with ordinary detergent. Avoid putting pressure on 

the lens. If the lens or other parts of the detector are defective, it/
they must be replaced.

Technical data

Input:
Power supply ............................................. 230 V AC 50 Hz ±10%
Power consumption .................................. 0.2 W

Performance:
Potentiometer ............................................ for test
Range ........................................................ Ø 16-32 m, 360°
Installation height ...................................... 4-8 m
Sensitivity  ................................................. 4 settings
Enclosure class ......................................... IP 54
Cable dimension (Ø14 mm max.) .............. 3 pcs. 5 x 2.5 mm

²

Ambient temperature ................................. -5°C to +50°C

Certification:
CE in accordance with .............................. EN 60669-2-1

The detector is delivered with a lens cover - can be 
adapted or removed for correct coverage.

Summary of Contents for SERVODAN

Page 1: ...Off under opvarmning Opvarmningstidens afslutning indikeres med 2 korte blink fra den grønne LED Tilslutningsskema Fig 5 Indstilling Fabriksindstilling Fig 6 Følsomhed High sensitivity DIP indstilling Følsomhed Off Off Minimum sensitivity Off On Low sensitivity On Off High sensitivity On On Maximum sensitivity Gå test For at kontrollere at sensoren detekterer korrekt er det muligt at udføre en gå ...

Page 2: ... ø3 7 ø6 5 ø11 ø16 5 meter ø0 25 ø2 5 ø4 7 ø8 5 ø14 ø20 6 meter ø0 3 ø3 ø5 5 ø10 ø17 ø24 7 meter ø0 4 ø3 5 ø7 ø11 5 ø20 ø28 8 meter ø0 5 ø4 ø7 5 ø14 ø22 ø32 F E D C B A H Height H 4 m 5 m 6 m 7 m 8 m A Ø0 20 Ø0 25 Ø0 30 Ø0 40 Ø0 50 B Ø2 00 Ø2 50 Ø3 00 Ø3 50 Ø4 00 C Ø3 70 Ø4 70 Ø5 50 Ø7 00 Ø7 50 D Ø6 50 Ø8 50 Ø10 00 Ø11 50 Ø14 00 E Ø11 00 Ø14 00 Ø17 00 Ø20 00 Ø22 00 F Ø16 00 Ø20 00 Ø24 00 Ø28 00 Ø3...

Page 3: ... Sie sich bei Störungen bzw Ausfall an einen Elektrofachkraft Änderungen vorbehalten Avertissement L installation et le montage d appareils électriques doivent exclusivement être exécutés par un électricien agréé En cas de défaut ou de perturbation du fonctionnement contacter un installateur électricien agréé Sous réserve de modifications Fig 5 Fig 7 Fig 6 Test Test 41 771 Motion detector 360 1 ch...

Page 4: ... warm up The end of the warm up time is indicated with two short flashes from the green LED For wiring diagram Fig 5 Setting Factory settings Fig 6 Sensitivity High sensitivity DIP Sensitivity setting Off Off Minimum sensitivity Off On Low sensitivity On Off High sensitivity On On Maximum sensitivity Walk test A walk test can be carried out to check that the detector is detecting correctly Select ...

Page 5: ...nale der grünen LED angezeigt Anschlussplan Abb 5 Einstellung Werkseinstellung Abb 6 Empfindlichkeit High sensitivity DIP Einstellung Empfindlichkeit Off Off Minimum sensitivity Off On Low sensitivity On Off High sensitivity On On Maximum sensitivity Geh Test Um zu kontrollieren ob der Melder Bewegungen korrekt erkennt kann ein sogenannter Geh Test durchgeführt werden Wählen Sie den Geh Test über ...

Page 6: ...age La fin du temps de démarrage est indiquée par deux clignotements courts de la DEL verte Schéma de câblage Fig 5 Paramétrage Paramétrage d usine Fig 6 Sensibilité Sensibilité élevée Réglage des contacteurs DIP sensibilité Off Off Sensibilité minimale Off On Sensibilité faible On Off Sensibilité élevée On On Sensibilité maximale Test de bon fonctionnement Pour contrôler que le détecteur fonction...

Page 7: ...Uppvärmningstidens avslutning indikeras med 2 korta blinkningar från den gröna lysdioden Kopplingsschema Fig 5 Inställning Fabriksinställning Fig 6 Känslighet High sensitivity DIP inställning känslighet Off Off Minimum sensitivity Off On Low sensitivity On Off High sensitivity On On Maximum sensitivity Gå test Det är möjligt att göra ett gå test för att kontrollera att sensorns detektering fungera...

Page 8: ...res det med at den grønne LED lampen blinker kort to ganger Tilkoblingsskjema Fig 5 Innstilling Innstillinger fra fabrikken Fig 6 Følsomhet High sensitivity DIP innstilling Følsomhet Off Off Minimum sensitivity Off On Low sensitivity On Off High sensitivity On On Maximum sensitivity Gå test For å kontrollere at sensoren registrerer riktig kan man utføre en gå test Velg gå test via Time potensiomet...

Reviews: