Control System
55
Service Manual – SC6500
™
I/O Table with Shop Measurements
A2 Control Board Assembly
Designation Pin ID
Wire ID/
Color
Description
Signal
Characteristics
Nominal
Value (when
activated)
Reference
To:
Acceptable
Range
Measured
Comments
Output
J1-1
BLU/GRA
Detergent
Pump2 (+)
Pulsed Voltage
0 or 36V
B- (ground)
see comment
below *
18-23V
Complex pulsed PWM signal
Measured in service test
mode.
Bidirectional
J1-2
BRN/BLU
CAN-L
Digital
Communication
see comment
see comment
2.37V
Protocol analyzer needed to
verify connection
Bidirectional
J1-3
GRN/BLU
CAN-H
Digital
Communication
see comment
see comment
2.64V
Protocol analyzer needed to
verify connection
Input
J1-4
ORN/RED
Speed Control
- Fault
Voltage
see comment
B- (ground)
see comment
Pulsed signal equal to the
fault code flashed by the
speed controllers built-in
status LED
Input
J1-5
GRN
B
Voltage
+36V
B- (ground)
31V - 38V
36.7V
Downstream of circuit
breaker F1, Key switch S1,
Diode D1, Seat Switch S2
and Battery Interlock Switch
S3
Output
J1-6
TAN/BRN
Detergent
Pump1 (-)
Pulsed Voltage
0 or 36V
B- (ground)
see comment
below *
11-17V
Line should alternate
between 0V and 36V when
detergent pump is activated.
Measured in service test
mode.
Output
J1-7
BLK/GRA
Detergent
Pump1 (+)
Pulsed Voltage
0 or 36V
B- (ground)
see comment
below *
18-23V
Line should alternate
between 0V and 36V when
detergent pump is activated
Input
J1-8
ORN
B
Voltage
+36V
B- (ground)
31V - 38V
37.46V
Downstream of circuit
breaker F1, switched through
key switch S1
Output
J1-9
ORN/GRA
Detergent
Pump2 (-)
Pulsed Voltage
0 or 36V
B- (ground)
see comment
below *
11-17V
Line should alternate
between 0V and 36V when
detergent pump is activated.
Measured in service test
mode
Input
J1-10
BLK
Battery -
Voltage
0V
B- (ground)
0 - 1V
0.04V
Vacuum motor running
Input
J1-11
RED/WHT Speed Control -
Motion
Voltage
0V (moving),
36V (not
moving)
B- (ground)
0 - 1V
(moving),
31 - 38V (not
moving)
24.8V N
0.006V FWD or REV