-28-
2-2
Mounting procedure ( Panel thickness range: 1.6 to 4.0mm)
(1)
External mounting
①
Process the mounting surface to cut out the openings in accordance with the respective mounting cutout drawings in
Page 30.
②
Fit the enclosed fixing bolts M6×35 to the unit. The number of bolts differs depending on the model.
③
Attach the enclosed packing cut to an appropriate length on the rear side of the unit. Affix metallic packing outside
the fixing bolts M6×35 as shown in the drawing of Page 31
④
Align the unit to fit the cutouts.
⑤
Fit the washers M6 and the fixing nuts M6 from inside the enclosure and secure them.
⑥
To ensure keep the panel interior airtight, caulk the gaps completely, if any.
⑦
Apply the enclosed “Alarm explanation sheet” to an appropriate place where readily visible.
Illustrated mounting procedure (Ex. PCN-30-2
)
Alarm code explanation sheet
Mounting surface
with cutouts
Washer M6
“accessory”
Fixing nuts M6
“accessory”
Spring washer M6
“accessory”
Packing
“accessory”
Fixing bolts
M6×35
“accessory”
Compressor Cooler