Technical Manual: EV-ABS - 000011 (Changes are subject to DCRN)
Section 7 - ADDRESS SETTING
To set the address of the device, set the address switch by adding
up the numbers on the left or right side. For example to set
address 24, set switch 4 and 5 to the ‘ON’ position. Switch 4 gives
you 8 and setting switch 5 adds 16 which gives the address 24. In
the example to the left, the address is set to 49 (1 + 16 + 32).
Section 8 - VOLUME
To set the volume, place the link in high or low volume position.
Section 9 - TONE CONFIGURATION
To set the sound pattern, set the tone selection switch according
to the table below. In the example to the left, tone 13 is selected
as switch 1 and 2 is on and switch 3 and 4 is off.
Date:
16.04.09
Issue:
7
• evolution
• EV-ABS
• addressable base sounder instruction manual
5
Tone
Alarm
Alert
SW1
SW2
SW3
SW4
1
Standard alarm tone. 750Hz/1000Hz alternating, 0.5s for each tone
10
ON
ON
ON
ON
2
Warble tone, general use. 850-950Hz sweep at 9Hz
10
OFF
ON
ON
ON
3
Sweep 1s (UK). 800Hz to 970Hz sweep over 1s, repeating
10
ON
OFF
ON
ON
4
French fire tone. 440Hz for 400ms, 554Hz for 100ms, repeating
10
OFF
OFF
ON
ON
5
German DIN tone. 1200Hz to 500Hz sweep over 1s, repeating
10
ON
ON
OFF
ON
6
Dutch tone. 500Hz to 1200Hz over 3.5s, 0.25s gap, repeating
10
OFF
ON
OFF
ON
7
Pulsed tone 1s on, 1s off at 750Hz
10
ON
OFF
OFF
ON
8
Continuous, 750Hz
10
OFF
OFF
OFF
ON
9
Continuous, 1000Hz
10
ON
ON
ON
OFF
10
Pulsed tone 1s on, 1s off at 1000Hz
10
OFF
ON
ON
OFF
11
Alternating at 2250Hz for 0.5s, 3000Hz, for 3s
10
ON
OFF
ON
OFF
12
Sweep 9Hz. 2250Hz to 3000Hz, repeating
10
OFF
OFF
ON
OFF
13
Sweep 1Hz. 2250Hz to 3000Hz, repeating
10
ON
ON
OFF
OFF
14
Continuous, 3000Hz
10
OFF
ON
OFF
OFF
15
Pulsed tone 1s on, 1s off at 3000Hz
10
ON
OFF
OFF
OFF
16
Silent (no sound)
10
OFF
OFF
OFF
OFF