background image

DW1401989  Rev.K2 

Dec 18, 2019 

Maintenance   

Routine inspection: Ensure the module is secure and undamaged. 

 

Operation Test 

The  purpose  of  the  Operational  Test  is  to  confirm  the  product’s  correct 

operation. 

1)

 

When carrying out site testing of the product, the control panel shall 

be set to “one-man-walk test mode” prior to the test. 

2)

 

Take  any  necessary  precautions  to  limit  the  sounding  of  the  alarm 

sounders/bells and any fire service summoning device. 

3)

 

Turn  on  the  external  inputs  connected  to  the  module,  and  confirm 

that  the  module  is  in  active  condition  and  the  input  LED  (red) 

illuminates.  Confirm  that  an  active  signal  is  transmitted  to  the 

control panel.     

Note: If the test cannot be carried out through the external inputs, test the 

area between terminal A+ and A-

or B+ and B-

to check the module. (In 

accordance  with  the subtype  setting, set  the  status either  0

Ω

  short  (for 

subtype 1-4), 2.2k

Ω

  short (for subtype 7-9), or open (for subtype 5-6).) 

4)

 

After  the  external  inputs  have  brought  the  module  into  the  active 

condition,  reset  the  external  inputs.  Confirm  that  the  module  goes 

back to the initial status after the external inputs are reset. 

5)

 

If subtype is set as 1-4, or 7-10, open between terminal A+ and A-

or 

B+  and  B-

  and  confirm  that  the  control  panel  detects  the  open 

circuit. If subtype is set as 5-10, short between terminal A+ and A-

or 

B+  and  B-

and  confirm  that  the  control  panel  detects  the  short 

circuit.   

6)

 

Short between terminal Lin+ (Lout+) and Lin- (Lout-), and the SCI 

LED  (yellow)  illuminates.  The  short  circuit  isolator  isolates  the 

devices connected after the short-circuited area, which makes these 

devices have no  response. Upon removal of  the  short condition, the 

area  is  automatically  connected  to  go  back  to  the  normal  standby 

status, and the SCI LED (yellow) turns off. 

 

FOR WARRANTY SERVICE, RETURN TO: 

 

OVERSEAS BUSINESS DIVISION, NITTAN COMPANY, LIMITED

 

1-54-5 SASAZUKA, SHIBUYA-KU, TOKYO 151-8535, JAPAN 

 

http://www.nittan.com

 

 

 

 

 

 

 

Specifications 

SLC Applied Voltage 

Rated range 20 to 38VDC 

SLC Current Consumption 

Standby 3.0mA   

Activated 16.9mA

max

 

SLC Line Impedance 

Up to 50 ohms 

Number of IDC Circuits 

1 x Class A or 2 x Class B 

IDC Circuit Rating 

15VDC, 2.2k ohms, 6.8mA (max) 

IDC Line Impedance 

Up to 50 ohms 

EOL Device 

RE-10k  (10k  ohms,  1/4W),  Class  B 

only 

2.2k ohms EOL required for each dry 

contact  switch  in  subtype  setting 

7,8,9,and 10 

SCI on Resistance 

0.2 ohms (max) 

SCI Fault Detection Threshold 

10V (min) 

SCI Isolation Current 

22mA (max) 

Visual Indicator (Status LED) 

Polling LED (GREEN) 

Input LED (RED) 

SCI LED (YELLOW) 

Ambient Installation 

Temperature   

0

  to 49

℃(

32°F to 120°F) 

 

Storage Temperature   

-20

  to 60

℃(

-4°F to 140°F) 

Max Relative Humidity 

Up to 93

  RH, non-condensing 

Environment 

Indoor dry use only 

Max. number of units per loop 

127 units 

Terminal 

Screw AWG12 to 22 

Address Setting 

EVA-AD2 Address Programmer 

Dimensions 

124mm H x 124mm W x 34.5mm D   

(4.882’’ H x 4.882’’ W x 1.358’’ D) 

(Mount  to  a  4’’  square  by  2

’’  deep 

box) 

Weight 

Approximately 153g (5.4oz) 

Conformity 

UL864 

 

 

 

 

 

 

 

 

Summary of Contents for EVA-DIP-SCI

Page 1: ...d Input LED red illuminates and the module communicates to the control panel the active status Trouble condition If an overcurrent occurs because SLC Signaling Line Circuit is shorted SCI LED yellow illuminates and the module communicates to the control panel the short status The module also communicates to the control panel the open short status of IDC depending on the Subtype Setting described b...

Page 2: ...ype depending on the wiring configuration as below The subtype is to be set through the Configurator for the control panel Sub Type Input Method Open circuit Detection Short circuit Detection Class Interrupt 1 Normally Open Yes No Class B Disabled 2 Enabled 3 Class A Disabled 4 Enabled 5 Normally Close No Yes Class B Disabled 6 Enabled 7 Normally Open Yes Yes Class B Disabled 8 Enabled 9 Class A D...

Page 3: ...rcuit detection is available It is a status that dry contact switches connected between A B and A B in EVA DIP SCI are OFF Two external inputs can be connected to the input line Resistor of 2 2k ohms RE 2 2k is an option and not included in this product B B A A Lin Lin Lout Lout Typical wiring for N O contacts only 2 2kΩ 2 2kΩ Loop TO NEXT DEVICE Loop FROM PANEL OR PREVIOUS DEVICE Figure 7 Normall...

Page 4: ...nel detects the short circuit 6 Short between terminal Lin Lout and Lin Lout and the SCI LED yellow illuminates The short circuit isolator isolates the devices connected after the short circuited area which makes these devices have no response Upon removal of the short condition the area is automatically connected to go back to the normal standby status and the SCI LED yellow turns off FOR WARRANT...

Page 5: ...s had been paid And the warranty period is three 3 years from the shipment from Nittan s factory 1 3 Notwithstanding anything to the contrary in this warranty terms Nittan shall not be liable to the customer by reason of any representation or implied warranty condition or other term or any duty at common law or under the express terms of this warranty terms for any consequential loss or damage whe...

Reviews: