Edit windows
Edit windows are used for modifying numeric parameter values. The selected character can be changed using the /
buttons. The cursor can be moved to the left using the button.
The direction of the cursor movement through the digits is right to left and the items wrap around. Changed values can be
validated by pressing the E button. The software checks if the entered value is valid; exiting the edit window is only
possible if the entered value is valid. If the entered value cannot be interpreted, the software sends an error message in
the bottom line (1) of the display.
Edit windows – button combinations
The following button combinations are available in the edit window:
1.
Reverting the parameters to the previously saved value ( + , pressed for 3 secs.).
2.
Restoring default parameters ( + , pressed for 3 secs.).
3.
Inserting the currently measured value to the edit window ( + , pressed for 3 secs.).
Only for certain parameters!
5.2.2
Menu structure
Main menu
BASIC SETUP
Parameter group of the basic measurement parameters
OUTPUT SETUP
Parameter group of the output parameters
SERVICE
Service functions, calibration, test and simulation
5.3.
D
ESCRIPTION OF PROGRAMMABLE FEATURES
5.3.1
Basic measurement settings
5.3.1.1
Source of transmitted PV (Primary Value)
Parameter: P01:
a
Menu path:
BASIC SETUP / DAMPING TIME
Default value:
AVERAGE
Description:
The selected value will be the basis for the analog and the digital (HART) transmitted Primary Value.
AVERAGE
SELECTED SENSOR
MAXIMUM
MINIMUM
All sensor data can be queried digitally, but the transmitted Primary Value can be selected in this parameter.