Battery
mode
Full load ≥ 84%
Output voltage
distortion
≤3% (100% linear load )
≤5% (100% nonlinear load )
Battery
Input battery
voltage
24VDC
36VDC
48VDC
72VDC
Internal battery
capacity
2
3
4
6
Internal battery
Sealed VRLA
Charge current
(A)
1.4
1.4
1.4
1.4
Table 14.
Work Environment
Model
1000-3000 series
Ambient Temperature
0~40C
Relative humidity
humidity humidityu
humidity
0~95% non-condensing
Altitude
>1500m, lower the rated power for use
Store temperature
-25~55C
Table 15.
Mechanical Specification
Model
Battery voltage
Dimension W*D*H (mm)
Net weight /Gross
Weight (kg)
NUPS23-1000
24VDC
440*430*86.5
11.5/15.1
NUPS23-1500
36VDC
14.5/18.1
NUPS23-2000
48VDC
440*572*86.5
17.5/22.2
NUPS23-3000
72VDC
440*692*86.5
19.8/25.5
Table 16.
Battery Runtimes (in Minutes) at 100% Load (ALL Models)
Model
Internal
Batteries
+ 1 EBP + 2 EBPs + 3 EBPs
+ 4 EBPs
1000
>3
<17
25
40
53
1500
>3
<17
25
40
53
2000
>3
<17
25
40
53
3000
>3
<17
25
52
69