Technical Instruction
Ex-Separator Module iXT0
Installation and connection
page 24
Ex-Separator Module iXT0 - rev. 02 / 28.08.2017
−
For installation in wet environments or in areas featuring the risk of flooding it
may be necessary to install extra protective measures such as a residual cur-
rent device (RCD) if required.
−
Check if the power supply of the units must be integrated into the facility's
emergency shutdown conception.
−
Transmitters and sensors shall be installed completely before feeding the
supply voltage.
−
Make sure that the installation is correct.
−
The installation shall be carried out by qualified personnel only.
−
Legal standards, provisions and technical regulations need to be observed.
13.1 Connection cable
Between sensor and transmitter
For the complete distance between the NIVUS sensors and transmitter
NivuFlow xxx use the cable Type
−
LiYC11Y 2x1.5 mm² + 1x2x0.34 mm² + PA
if possible.
Between sensor and iXT0
Maximum cable lengths between sensors and iXT0 if using the NIVUS standard
cable LiYC11Y 2x1.5 mm² + 1x2x0.34 mm² + PA:
−
150 meters (see Fig. 13-1)
−
Use of overvoltage protection elements:
o
Single-side: 135 meters
o
Double-side: 120 meters