Instruction Manual
NivuCompact
page 18
NivuCompact – Rev. 05 as of 31.10.2012
6.3
Transmitter Connection
When opening the NivuCompact enclosure, please strictly avoid moisture
(dew, drops etc.) or dirt to get into the NivuCompact electronics compartment.
Water or dirt must not leak into the terminal housing. Please seal the clamp
housing in a way that neither water nor dirt might leak in.
An incorrect or faulty sealing does not ensure the indicated protection.
Connecting and/or utilising the NivuCompact in another way than described in
this instruction manual may interfere with standard protection and lead to
defects in the equipment.
6.3.1
Maximum load for 2-wire and 3/4-wire operation
Fig. 6-3
Maximum permissible line resistance at 2- wire connection
(table refers to 4-20 mA output at max. 22 mA in case of error)
Fig. 6-4
Maximum load at 3- wire connection
We recommend to use a shielded cable such as LIYCY or A-2Y(L)2Y to connect
the NivuCompact.