NivuLink Compact - Document revision 02 / 06.08.2020
6.10 Digital Input Clamp RCP0 750 1405
(Only for Art. NLC0 CLOG)
Number of digital inputs
16
Total number of channels (input terminals)
16
Signal type
Current
Current signal type
DC 24 V
Sensor connection
16 x (1-wire)
Input characteristic
Positive-switching
Input filter (digital)
3 ms
Typ. input current per channel with
signal (0)
0.6 mA
Min. input current per channel with
signal (1)
2.1 mA
Max. input current per channel with
signal (1)
2.4 mA
Voltage range for signal (0)
DC −3 … +5 V
Voltage range for signal (1)
DC 15 … 30 V
Max. data width of input data (internal)
16 Bit
System supply voltage
DC 5 V; via data contacts
Power consumption system supply (5 V)
25 mA
System and Sensor supply voltage
)
Field power supply
DC 24 V (-25 … +30 %); via power con-
tacts (fed through blade contact; distribu-
tion via spring contact)
Electrical isolation
500 V system/field
Indicating elements
LED (1-16) Green: Status DI 1 … DI 16
Number of input power contacts
2
Number of output power contacts
2
Current carrying capacity of power contacts
10 A
Tab. 6-14 Technical Data – Digital input clamp