Connecting your equipment and first usage

4

4.1 Connecting external battery

1. 

It is recommended to install a DC Breaker in a positive battery line. 

The rating of the DC Breaker must be at least 75Ah to guarantee safe 

operation without interruption. Keep the DC Breaker off.

NOTE!

For the user operation safety we strongly recommend that you should use 

tapes to isolate the battery terminals before you start to operate the UPS.

 

A. Single battery connection

When using a single battery its voltage must be equal to the Nominal DC 

Voltage of the unit.

 

B. Multiple batteries in series connection

All batteries must be equal in voltage and amp hour capacity. The sum of 

their voltages must be equal to the nominal DC Voltage of the unit.

 

C. Multiple batteries in parallel connection

Each battery’s voltage must be equal to the Nominal DC Voltage of the unit.

It’s very important for system safety and efficient operation to use 

appropriate external battery cable. To reduce risk of injury, external 

battery cables should be rated for 75° C or higher. Do 

NOT

 use 

copper cables with less than 10mm in cross sectional area!

CAUTION

2. 

Make sure to connect the polarity of battery side and the unit correctly. 

Positive pole (Red) of battery to the positive terminal (+) of the unit. 

Negative pole (Black) of battery to the negative terminal (-) of the unit.

3. 

After connecting the battery to the UPS use tape to isolate the external 

battery terminals.

4.2 Connecting to utility and charge

Plug in the AC input cord to the wall outlet. The unit will automatically 

charge the connected external battery even though the unit is off.

The unit may have output power when is connected to the utility, 

even though it is powered off. To completely cut off the output 

power, please switch off the unit and disconnect.

CAUTION

4.3 Starting the UPS

Please make sure that the battery is connected before you turn ON the 

UPS. If your battery is connected you can turn ON the ON/OFF switch 

and charge the battery or batteries at least 8 hours for a full load.

NOTE!

The battery or batteries connected to the UPS must be at least 38Ah each to 

guarantee safe operation without interruption.

Summary of Contents for Aira 600

Page 1: ...Aira 600 User Manual Manual de utilizare UPCSTLP860TAICP01B Before using this product carefully read all product documentation and retain it for future reference 300 1...

Page 2: ...lectronic equipment from physical damage and will provide emergency battery backup power to prevent data loss in the event of power problems NOTE Before installation please inspect the unit Be sure th...

Page 3: ...rst press the OFF Enter button to disconnect the mains Prevent fluids or other foreign objects from entering the inside of the UPS system Maintenance service and faults The UPS system operates with ha...

Page 4: ...duce risk of injury external battery cables should be rated for 75 C or higher Do NOT use copper cables with less than 10mm in cross sectional area CAUTION 2 Make sure to connect the polarity of batte...

Page 5: ...r 4 seconds to turn off the UPS The UPS will keep charging the battery if the utility power is normal Please pull out the power cord if you want to turn off the UPS completely 5 6 Under back up mode w...

Page 6: ...e call for service UPS emits urgent beep battery capacity indicator flickers Low battery 1 Charge batteries 2 Replace batteries 3 Call for service NOTE If any abnormal situations occur that are not li...

Page 7: ...ata at Mul umim pentru c a i ales produsele noastre V rug m citi i cu aten ie manualul de utilizare nainte de a pune n func iune acest produs Concentr ndu ne pe calitate la pre uri competitive constr...

Page 8: ...ela i tip de baterii Nu ncerca i s distruge i bateriile prin arderea lor Acest lucru poate cauza explozia bateriilor V rug m s nlocui i siguran a numai cu acela i tip de siguran i amperaj pentru a evi...

Page 9: ...tensiune chiar dac este oprit Pentru a ntrerupe complet tensiunea v rugam sa opri i UPS ul i s l deconecta i de la aparate ATEN IE 4 3 Pornirea UPS ului Asigura i v c bateria este conectat nainte de...

Page 10: ...care are nevoie echipamentul s nu dep easc capacitatea UPS ului Alarma va porni i va continua s sune dac capacitatea este dep it Iar dac supra nc rcarea este cu mult peste limita UPS ului el se va opr...

Page 11: ...nc rcat Nu folosi UPS ul Las l la nc rcat 10 ore i testeaz din nou Dac apare aceea i problem UPS ul are nevoie de o baterie nou Butonul nu func ioneaz 1 CPU ul UPS ului nu func ioneaz 2 Butonul are o...

Page 12: ...oca ia Semn tura i nume simbolul de conformitate european Tommy Lee Aira 600 UPCSTLP860TAICP01B EU Declaration of Conformity We manufacturer importer declare that the product Aira 600 UPCSTLP860TAICP0...

Page 13: ......

Reviews: