Bypass voltage range setting
HLS
INPUT
26 0
Vac
Parameter 2:
Set the acceptable high voltage
point and acceptable low voltage point for
Bypass mode by pressing the Down key or
Up key.
HLS:
Bypass high voltage point
230-264: setting the high voltage point in
parameter 3 from 230Vac to 264Vac. (Default:
264Vac)
LLS:
Bypass low voltage point
170-220: setting the low voltage point in
parameter 3 from 170Vac to 220Vac. (Default:
170Vac)
08:
Bypass frequency range setting
HLS
INPUT
53 0
Hz
Parameter 2:
Set the acceptable high fre-
quency point and acceptable low frequency
point for Bypass mode by pressing the
Down key or Up key.
HLS:
Bypass high frequency point
51-55Hz: setting the frequency high loss
point from 51Hz to 55HZ(Default: 53.0Hz).
LLS:
Bypass low Frequency point
45-49Hz: setting the frequency low loss point
from 45Hz to 49HZ(Default: 47.0Hz)
09:
Programmable outlets enable/disable
d I S
P1
Parameter 2:
Enable or disable the program-
mable outlets function.
You may choose the following two options:
ENA:
Programmable outlets enable
DIS:
Programmable outlets disable (Default)
10:
Programmable outlets setting
M
P1
999
Parameter 2:
Set up backup time limits for
programmable outlets.
0-999:
setting the backup time limits in
minutes from 0-999 for programmable
outlets which connect to non-critical
devices on battery mode. (Default: 999).
11:
Autonomy limitation setting
M
999
Parameter 2:
Set up backup time on battery
mode for general outlets.
0-999:
setting the backup time in minutes from
0-999 for general outlets on batt. mode.
DIS:
Disable the autonomy limitation and
the backup time will depend on battery
capacity. (Default)
NOTE:
When setting as “0”, the backup time
will be only 10 seconds.
12:
Battery total AH setting
bAH 7
Parameter 2:
Set up the battery total AH of
the UPS.
7-999:
setting the battery total capacity
from 7-999 in AH. Please set the correct
battery total capacity if external battery
bank is connected.
EXAMPLE:
if you use Balder 1500
together with one battery cabinet with 6
pcs of 12V7Ah batteries (two strings of 3
batteries), total battery AH setting will be:
9AH (UPS battery string capacity) + 2x7AH
(2 strings of 7Ah batteries inside battery
cabinet) = 23AH
13:
Maximum charger current setting
CHA
If you use external battery pack please set
the appropriate charging current based
on battery capacity used. Please use the
following table as reference: