08: Bypass mode setting
Parameter 2:
OPN:
Bypass allowed. When selected, UPS
will run at Bypass mode depending on bypass
enabled/disabled setting.
FBD:
Bypass not allowed. When selected, it’s
not allowed for running in Bypass mode under
any situations.
Parameter 3:
ENA:
Bypass enabled. When selected, Bypass
mode is activated.
DIS:
Bypass disabled. When selected,
automatic bypass is acceptable, but manual
bypass is not allowed. Manual bypass means
users manually operate UPS for Bypass mode.
For example, press OFF button in AC mode to
turn into Bypass mode.
09: Battery backup time setting
Parameter 3:
000~999:
Set the maximum backup time
from 0 min to 999 min. UPS will shut down to
protect battery after backup time arrives.
DIS:
Disable battery discharge protection and
backup time will depend on battery capacity.
The default value is DIS.
10: Reserved
Reserved
11: Reserved
Reserved
12: Hot stand-by function enable/disable
Parameter 2:
HS.H
Enable or disable Hot standby function.
You may choose following two options in
Parameter 3:
YES:
Hot standby function is enabled. It means
that the current UPS is set to host of the hot
standby function, and it will restart after AC
recovery even without battery connected.
NO:
Hot standby function is disabled. The UPS
is running at normal mode and can’t restart
without battery
13: Battery voltage adjustment
Parameter 2:
Select “Add” or “Sub” function to
adjust battery voltage to the real value.
Parameter 3:
the voltage range is from 0V to
5.7V, the default value is 0V.
14: Charger voltage adjustment
Parameter 2:
you may choose Add or Sub to
adjust charger voltage
Parameter 3:
the voltage range is from 0V to
9.9V, the default value is 0V.
NOTE!
*Before making voltage adjustment, be sure to disconnect all batteries first to get
the accurate charger voltage.
*We strongly suggest to use the default value (0). Any modification should be
suitable to battery specifications.
15: Inverter voltage adjustment
Parameter 2:
you may choose Add or Sub to
adjust inverter voltage
Parameter 3:
the voltage range is from 0V to
6.4V, the default value is 0V.