40
Fault code is shown as
43. The icon
OVER LOAD
lights on LCD display
and alarm beeps
continuously.
UPS is overload too
long and becomes
fault. Then UPS shut
down automatically.
Remove excess loads from
UPS output and restart it.
Fault code is shown as
14, the icon
SHORT
lights on LCD display,
and alarm beeps
continuously.
The UPS shut
down automatically
because short circuit
occurs on the UPS
output.
Check output wiring and if
connected devices are in
short circuit status.
Fault code is shown
as 1, 2, 3, 4, 11, 12,
13, 14,1A, 21, 24, 35,
36, 41, 42 or 43 on
LCD display and alarm
beeps continuously.
A UPS internal fault
has occurred. There
are two possible
results:
1. The load is still
supplied, but directly
from AC power via
bypass.
2. The load is no
longer supplied by
power.
Contact your dealer.
Battery backup time is
shorter than nominal
value.
Batteries are not fully
charged.
Charge the batteries
for at least 7 hours and
then check capacity. If
the problem still persists,
consult your dealer.
Batteries defect.
Contact your dealer to
replace the battery.
The icon
and
flash on LCD display
and alarm beeps every
second.
Fan is locked or not
working; or the UPS
temperature is too
high.
Check fans and notify
dealer.
Disposal of Old Electrical & Electronic Equipment
(Applicable in the European Union and other European countries with
separate collection systems)
This symbol on the product or on its packaging indicates that this product shall
not be treated as household waste.
Instead it shall be handed over to the applicable collection point for the recycling
of electrical and electronic equipment.
By ensuring this product is disposed of correctly, you will help prevent potential
negative consequences for the environment and human health, which could
otherwise be caused by inappropriate waste handling of this product.
The recycling of materials will help to conserve natural resources.
Summary of Contents for Balder 10000
Page 43: ......