03:
Output frequency settings
Parameter 2: You may set the initial fre-
quency on battery mode:
BAT 50:
presents output frequency of 50Hz
BAT 60:
presents output frequency of 60Hz
If converter mode is enabled, you may
choose the following output frequency:
CF 50:
present output frequency is 50Hz
CF 60:
present output frequency is 60Hz
04:
ECO enable/disable
Parameter 2: Enable or disable ECO
function. You may choose the following
two options:
ENA:
ECO mode enable
DIS:
ECO mode disable (Default)
05:
ECO voltage range setting
Parameter 2: Set the acceptable high
voltage point and low voltage point
for ECO mode by pressing Down key or
Up key.
HLS:
High loss voltage in ECO mode in
parameter 2.
The setting range in parameter 3 is from
+7V to +24V of the nominal voltage.
(Default: +12V)
LLS:
Low loss voltage in ECO mode in
parameter 2.
The setting range in parameter 3 is from
-7V to -24V of the nominal voltage.
(Default: -12V)
06:
Bypass enable/disable when UPS is off
Parameter 2: Enable or disable Bypass
function. You may choose the following
two options:
ENA:
Bypass enable
DIS:
Bypass disable (Default)
07:
Bypass voltage range setting
Parameter 2: Set the acceptable high
voltage point and acceptable low voltage
point for Bypass mode by pressing the
Down key or Up key.
HLS:
Bypass high voltage point
230-264:
setting the high voltage point
in parameter 3 from 230Vac to 264Vac.
(Default: 264Vac)
LLS:
Bypass low voltage point
170-220:
setting the low voltage point
in parameter 3 from 170Vac to 220Vac.
(Default: 170Vac)
08:
Bypass frequency range setting
Parameter 2: Set the acceptable high
frequency point and acceptable low
frequency point for Bypass mode by
pressing the Down key or Up key.
HLS:
Bypass high frequency point
51-55Hz:
setting the frequency high
loss point from 51Hz to 55HZ(Default:
53.0Hz).
LLS:
Bypass low Frequency point
45-49Hz:
setting the frequency low loss
point from 45Hz to 49HZ(Default: 47.0Hz)
09:
Programmable outlets enable/disable
Parameter 2: Enable or disable the
programmable outlets function.
You may choose the following two
options:
ENA:
Programmable outlets enable
DIS:
Programmable outlets disable
(Default)