Programmable outlets setting
0-999:
you can set the backup time
limit in minutes from 0-999 for
programmable outlets which are
connected to non-critical devices on
battery mode (Default: 999).
12:
Autonomy limitation setting
Set up backup time on battery mode
for general outlets.
0-999:
setting the backup time in
minutes from 0-999 for general
outlets on battery mode.
DIS:
Disable the autonomy limitation
and the backup time will depend on
battery capacity. (Default)
Note: When setting as “0”, the
backup time will be only 10 seconds.
13:
Battery total AH setting
Set up the battery total AH of the
UPS.
7-999:
setting the battery total
capacity from 7-999 in AH.
14:
Maximum charger current setting
Set up the maximum charger current.
When the UPS is equipped with
additional charger, the available
setting options are 2/3/4.
2/3/4:
setting the maximum charger
current in 2/3/4 Ampere.
When the UPS is long run model,
the available setting options are
1/2/4/6/8.
1/2/4/6/8:
setting the maximum
charger current in 1/2/4/6/8
Ampere. (Default: 8A)
15:
Charger Boost voltage setting
Set up the charger boost voltage.
225-240:
setting the charger boost
voltage from 225 to 240(unit: 0.01V/
cell). (Default: 236)
16:
Charger Float voltage setting
Set up the charger float voltage.
220-233:
setting the charger float
voltage from 220 to 233(unit: 0.01V/
cell). (Default: 228)