Important Safety Warnings
3
Please read carefully the following instructions before
installing the unit. Do not operate this unit before
reading through all safety information and operating
instructions carefully!
Preparation
This battery bank is connected to an UPS. There
will be voltage at the output terminals if the
UPS is turned on even if the input AC Mains is not
available.
Make sure that the AC Utility outlet is correctly
grounded.
Do not try to repair the unit yourself, contact your
local supplier or your warranty will be void.
Installation and connection warnings
Use a certified input power cable with the correct
plugs and sockets.
To eliminate any overheating of the battery bank,
keep all ventilation openings free from obstruction
and do not place any foreign objects on top of the
battery bank. Keep the battery bank 20 cm away
from the wall.
Make sure the battery bank is installed within the
proper environment as specified: 0-40°C and 30-
90% non-condensing humidity.
Storage and maintanance
The warranty for this battery bank will be void if
water or other liquid is spilt or poured directly onto
the battery bank. Similarly, warranty is void if any
damage to the battery bank occurs due to foreign
objects which are deliberately or accidentally
inserted into the battery bank enclosure.
The battery will discharge naturally if the system is
unused for a period of time. It should be recharged
every 2-3 months if unused. If this is not done, then
the warranty will be void. During normal operation,
the batteries will be automatically charged.
Servicing of batteries should be performed or
supervised by trained personnel only. When
replacing batteries, replace with the same quantity,
type & capacity.
The unit contains no user-serviceable parts. If
the battery service life has been exceeded, the
batteries must be replaced. In this case, please
contact your dealer.
Do not install the battery bank under direct
sunlight. Your warranty will be void if the
batteries fail due to overheating.
This battery bank is designed for indoor use only.
This battery bank is not designed for use in dusty,
corrosive and salty environment.
Cautions regarding battery installation