  Some warning alarms can’t be muted unless the error is fixed. Please refer 

to section 3-3 for details.

 3.4.11.

 

Operation in Fault mode

  When Fault LED illuminates and the buzzer beeps continuously, it means 

that there is a fatal error with the UPS. Users can get the fault code from 

“DATA LOG” menu. Please refer to the Section 3-2-6 for details.

  Please check the loads, wiring, ventilation, utility, battery and so on 

after the fault occurs. Don’t try to turn on the UPS again before solving the 

issue. If the problems can’t be fixed, please contact the distributor or service 

personnel immediately.

  For emergency case, please cut off connection from utility,  external 

battery, and output immediately to avoid possible damage to the UPS or 

equipment.

 3.4.12.

 

Operation in maintaining bypass mode

NOTE! 

This operation is only available for professional or qualified technicians!

When the UPS needs to repair or service and when the load can’t be shut off, 

the UPS needs to turn to maintenance mode.

  First, turn off the UPS.

  Second, remove the cover of maintenance bypass switch on the panel.

  Third, turn the maintenance switch to “BPS” position and turn off the UPS 

input breaker and output breaker.

3.5. Parallel operation
NOTE! 

Ranger series supports parallel operations up to 4 units. Parallel operation should 

be done only by authorized personal only. Please contact technician that installed 

the UPS if you need to start parallel operations.

  3.5.1.

 

Parallel system initial startup

Please make sure that all of the running UPSs are parallel models and have 

the same configuration.

  Turn on each UPS in AC mode respectively (Refer to section 3.4.1). Then, 

measure the inverter output voltage of each phase for each UPS with a 

multi-meter. Calibrate the inverter output voltage by configuring inverter 

voltage adjustment (Refer to SETTING 

 Advance 

► Maintainer ► 

VOL 

CALI 

► Inventer CALI 

screen) in LCD menu until the inverter output voltage 

difference of each UPS is within 1V or less.

  Turn off each UPS (Refer to section 3.4.7). Then, follow the wiring 

procedure in section 2.5.

  Connect each UPS one by one with the data cable and share current 

cable, as shown in below picture:

  Turn on the parallel system in AC mode:

    a)  Turn on the line input breaker of each UPS (for dual input, also 

turn on bypass input breaker). After all UPSs enter to bypass mode, 

measure the output voltage between two UPSs for the same phase 

to make sure the phase sequence is correct. If these two voltage 

differences are near to zero, that means all connections are met. 

Otherwise, please check if the wirings are connected correctly.

    b)  In Bypass Mode, check INFO Menu to see if UPS communicates 

correctly (“INFO”-> “BASIC” -> “PAGE 2”). PAR State will be Parallel 

and PAR ID will be 1 and 2:

Basic Information Page1

    c)Turn on the output breaker of each UPS.

    d)  Turn on each UPS in turns. After a while, the UPSs will enter to AC 

mode synchronously and then, the parallel system is now complete. 

Summary of Contents for Ranger 180KT

Page 1: ...Ranger Series User Manual 180KT 3 Phase IN 3 Phase OUT UPS UP33TOP118ZRAAZ01B 237 35 21 0 Before using this product carefully read all product documentation and retain it for future reference...

Page 2: ...EMC instructions 5 1 1 Transportation and storage 5 1 2 Preparation 5 1 3 Installation 5 1 4 Connection warnings 6 1 5 Operation 7 1 6 Standards 7 2 Installation and operation 8 2 1 Unpacking and insp...

Page 3: ...lation An integral emergency shutoff switch which prevents additional load from the UPS in any mode of operation should be implemented during the installation Secure the grounding earthing wire before...

Page 4: ...ee phase input NOTE There can be no derivation in the line that goes from the Backfeed Protection to the UPS as the standard safety would be infringed Warning labels should be placed on all primary po...

Page 5: ...t and battery set in their original packaging because they have been designed to provide maximum protection during transportation and storage Installation and operation 2 2 2 Wiring terminal view 1 RS...

Page 6: ...the output power will be derated by following the table Vertical No vibration and the degree of deviation from vertical shouldn t be more than 5 Space It s requested to have a clearance of approx 50 c...

Page 7: ...l block wiring diagram for HV 180KT NOTE Please install the output breaker between the output terminal and the load and the breaker should be qualified with leakage current protective function if nece...

Page 8: ...ration make sure that the two strings of batteries are connected correctly in order of GND terminals and the breaker of the battery pack is at ON position only in case of external battery packs presen...

Page 9: ...that takes a few seconds After initialization the main screen will display as shown below On the bottom there are five icons to represent five sub menus CONTROL MEASURE SETTING INFO DATALOG Main scree...

Page 10: ...te All if the UPS is mute already Touch Yes activate audio function or No to keep mute Touch Back to return to CONTROL screen Mute All Cancel Mute All ON OFF Charger It will show Turn on Charger when...

Page 11: ...al time value of output power factor in R S and T phases 3 2 4 Setting screen This sub menu is used to set the parameters of UPS Touch the icon to enter setting menu page There are 2 options Basic and...

Page 12: ...the acceptable input frequency will be fixed at the range of 40 70Hz This setting value will show on the status bar Service Contact Set the name of contact person and the maximum length is 18 characte...

Page 13: ...sword is wrong it will ask to enter again Password error page Advance Setting Menu page There are three sub menus under Advance User setting ELECTRONIC BATTERY and MISCELLANEOUS ELECTRONIC Electronic...

Page 14: ...When neutral is restored the alarm will NOT be muted automatically and the UPS will NOT go back to normal mode automatically ISO Compensation When UPS is connected to output isolation it will compensa...

Page 15: ...then utility restores the UPS will return to line mode Disable After Disable is set once UPS shutdown occurs and the utility restores the UPS will not automatically turn on Shutdown Delay Min UPS wil...

Page 16: ...ble ECO function Auto Restart Enable disable auto restart function PARAMETER information Parameter Information Page1 Line Voltage Range The acceptable line input voltage range Line FRE Range The accep...

Page 17: ...S operates in Bypass mode and supplies power to the load via the bypass NOTE When UPS is in Bypass mode the output voltage will draw power from utility after you switch on the input breaker In Bypass...

Page 18: ...may vary from different environment temperature and load type When setting backup time for 16 5 hours default value from LCD menu after discharging 16 5 hours UPS will shut down automatically to prote...

Page 19: ...nician that installed the UPS if you need to start parallel operations 3 5 1 Parallel system initial startup Please make sure that all of the running UPSs are parallel models and have the same configu...

Page 20: ...d in each UPS and then turn off the running system All UPSs will transfer to Bypass mode Remove all the maintenance bypass covers and set the maintenance switches from UPS to BPS position Turn off all...

Page 21: ...current in A phase 34 Synchronous trigger signal failure 75 INV IGBT over current in B phase 35 Parallel communication loss 76 INV IGBT over current in C phase 36 Parallel output current unbalance 77...

Page 22: ...UPS output and restart it Troubleshooting 4 Problem Possible cause Solutions Fault code is shown as 14 15 16 17 18 or 19 The UPS shut down automatically because short circuit occurs on the UPS output...

Page 23: ...capacitor such as BUS capacitors Only persons adequately familiar with batteries and with the required precautionary measures may replace batteries and supervise operations Unauthorized persons must...