Turn on the parallel system in Battery mode:
a) Turn on the battery breaker and output breaker of each UPS.
b) Turn on any UPS. A few seconds later, the UPS will enter to battery
mode.
c) Turn on another UPS. A few seconds later, the UPSs enter to Battery
mode and add to the parallel system.
d) If you have the third UPS, follow the same procedure of c). Then, the
parallel system is complete.
NOTE!
If you would like to have more information regarding the parallel operation, please
contact your supplier or service center for detail parallel operation instruction.
3.5.2.
Add new units into the parallel system
•
You can’t add one new unit into the parallel system when whole system is
running. You must cut off the load and shutdown the system.
•
Make sure all of the UPS are the parallel models, and follow the wiring
refer to section 2.5.
•
Install the new parallel system refers to the previous section.
3.5.3.
Remove units from the parallel system
There are two methods to remove units from the parallel system:
•
First method:
a) Touch “CONTROL”
►
“Turn off UPS” and select “Yes” to turn of
the UPS. Then, the UPS will enter into Bypass mode or No Output
mode without output.
b) Turn off the output breaker of this unit, and then turn off the input
breaker of the same unit.
c) After it shuts down, you can turn off the battery breaker and
remove the data and share current cables. And then remove the
unit from the parallel system.
•
Second method:
a) If the bypass is abnormal, you can not remove the UPS without
interruption. You must cut off the load and shut down the system first.
b) Make sure the bypass setting is enabled in each UPS and then
turn off the running system. All UPSs will transfer to Bypass mode.
Remove all the maintenance bypass covers and set the maintenance
switches from “UPS” to “BPS” position. Turn off all the input
breakers and battery breakers in parallel system.
c) Turn off the output breaker and remove the data cable and share
current cable of the UPS which you want to remove. Now, you can
remove the UPS from parallel system.
d) Turn on the input breaker of the remaining UPS and the system will
transfer to Bypass mode. Set the maintenance switches from “BPS”
to “UPS position and put the maintenance bypass covers back on.
e) Turn on the remaining UPS according to the previous section.
● Before turning on the parallel system to activate inverter, make sure
that all unit’s maintenance switch at the same position.
● When parallel system is turned on, please do not operate the
maintenance switch of any unit.
● Please
DO NOT
enable the ECO mode in parallel system.
WARNING (Only for the parallel system)
3.6. Fault Code
Fault code Fault event
Fault code Fault event
01
Bus start failure
43
Overload
02
Bus over
46
Incorrect UPS setting
03
Bus under
47
MCU communication
failure
04
Bus unbalance
48
Two DSP firmware
versions are
incompatible in parallel
system.
06
Converter over current
60
Bypass phase short
circuited
11
Inverter soft start failure
61
Bypass SCR short
circuited
12
High inverter voltage
62
Bypass SCR open
circuited
15
Inverter B output(line to
neutral) short circuited
63
Voltage waveform
abnormal in A phase
16
Inverter C output(line to
neutral) short circuited
64
Voltage waveform
abnormal in B phase
17
Inverter A-B output (line
to line) short circuited
65
Voltage waveform
abnormal in C phase
18
Inverter B-C output (line
to line) short circuited
66
Inverter current detect
abnormal