background image

6

7

1.4. Connection warnings

• 

There is no standard backfeed protection inside of the UPS. However, 

there are relays on the Input to cut off line voltage while the neutral is still 

connect to UPS.

UPS

Main

Input

Input Rly

Input Rly

N

L1
L2
L3

Bypass

Input

N

L1
L2
L3

UPS

Main

Input

Input Rly

Input Rly

L1
L2
L3

N

Bypass

Input

Input Rly

L1

N

UPS

Main

Input

Input Rly

L1

Bypass

Input

N

Input Rly

L1

N

3:3 phase

3:1 phase

1:1 phase

• 

This UPS should be connected with TN grounding/earthing system.

• 

The power input for this unit must be three-phase rated in accordance 

with the equipment nameplate. It also must be suitably grounded.

High leakage current! 

Earth connection essential before connecting supply!

WARNING

• 

Use of this equipment in medical instrument of any life-sustaining 

equipment where failure of this equipment can reasonably be expected to 

cause the failure of the life-sustaining equipment or to significantly affect its 

safety or effectiveness is not recommended. Do not use this equipment in 

the presence of a flammable mixture with air, oxygen or nitrous oxide.

• 

Connect grounding terminal of UPS to a grounding electrode conductor.

• 

In accordance with safety standard EN-IEC 62040-1, installation has to 

be provided with a 

«Backfeed Protection»

 system, as for example a contactor, 

which will prevent the appearance of voltage or dangerous energy in the input 

mains during a mains fault (respect the wiring diagram of 

«Backfeed Protection»

 

depending if the equipment is with signal or three phase input).

NOTE!

There can be no derivation in the line that goes from the «Backfeed Protection» to 

the UPS, as the standard safety would be infringed.

• 

Warning labels should be placed on all primary power switches installed 

in places away from the unit to alert the electrical maintenance personnel of 

the presence of a UPS in the circuit. The label will bear the following or an 

equivalent text:

Before working on this circuit

  1. Isolate Uninterruptible Power Supply (UPS)

   2. Then check for Hazardous Voltage between all terminals including the 

protected earth.

 Risk of Voltage Backfeed

1.5. Operation

• 

Do not disconnect the grounding/earthing conductor cable on the UPS or 

the building wiring terminals under any circumstance.

• 

The UPS system features its own, internal current source (batteries). The 

UPS output sockets or output terminal blocks may be electrically live even if 

the UPS system is not connected to the building mains/live wires . 

• 

In order to fully disconnect the UPS system, first press the “OFF” button 

and then disconnect the mains/live wires .

• 

Ensure that no liquid or other foreign objects can enter into the UPS 

system.

1.6. Standards

*Safety

IEC/EN 62040-1

*EMI

Conducted Emission

IEC/EN 62040-2

Category C3

Radiated Emission

IEC/EN 62040-2

Category C3

*EMS

ESD

IEC/EN 61000-4-2

Level 4

RS

IEC/EN 61000-4-3

Level 3

EFT

IEC/EN 61000-4-4

Level 4

SURGE

IEC/EN 61000-4-5

Level 4

CS

IEC/EN 61000-4-6

Level 3

Power-frequency Magnetic field

IEC/EN 61000-4-8

Level 4

Low Frequency Signals

IEC/EN 61000-2-2

This is a product for commercial and industrial application and the 

second environment installation restrictions or additional measures may 

be needed to prevent disturbances.

WARNING

Summary of Contents for Ranger 180KT

Page 1: ...Ranger Series User Manual 180KT 3 Phase IN 3 Phase OUT UPS UP33TOP118ZRAAZ01B 237 35 21 0 Before using this product carefully read all product documentation and retain it for future reference...

Page 2: ...EMC instructions 5 1 1 Transportation and storage 5 1 2 Preparation 5 1 3 Installation 5 1 4 Connection warnings 6 1 5 Operation 7 1 6 Standards 7 2 Installation and operation 8 2 1 Unpacking and insp...

Page 3: ...lation An integral emergency shutoff switch which prevents additional load from the UPS in any mode of operation should be implemented during the installation Secure the grounding earthing wire before...

Page 4: ...ee phase input NOTE There can be no derivation in the line that goes from the Backfeed Protection to the UPS as the standard safety would be infringed Warning labels should be placed on all primary po...

Page 5: ...t and battery set in their original packaging because they have been designed to provide maximum protection during transportation and storage Installation and operation 2 2 2 Wiring terminal view 1 RS...

Page 6: ...the output power will be derated by following the table Vertical No vibration and the degree of deviation from vertical shouldn t be more than 5 Space It s requested to have a clearance of approx 50 c...

Page 7: ...l block wiring diagram for HV 180KT NOTE Please install the output breaker between the output terminal and the load and the breaker should be qualified with leakage current protective function if nece...

Page 8: ...ration make sure that the two strings of batteries are connected correctly in order of GND terminals and the breaker of the battery pack is at ON position only in case of external battery packs presen...

Page 9: ...that takes a few seconds After initialization the main screen will display as shown below On the bottom there are five icons to represent five sub menus CONTROL MEASURE SETTING INFO DATALOG Main scree...

Page 10: ...te All if the UPS is mute already Touch Yes activate audio function or No to keep mute Touch Back to return to CONTROL screen Mute All Cancel Mute All ON OFF Charger It will show Turn on Charger when...

Page 11: ...al time value of output power factor in R S and T phases 3 2 4 Setting screen This sub menu is used to set the parameters of UPS Touch the icon to enter setting menu page There are 2 options Basic and...

Page 12: ...the acceptable input frequency will be fixed at the range of 40 70Hz This setting value will show on the status bar Service Contact Set the name of contact person and the maximum length is 18 characte...

Page 13: ...sword is wrong it will ask to enter again Password error page Advance Setting Menu page There are three sub menus under Advance User setting ELECTRONIC BATTERY and MISCELLANEOUS ELECTRONIC Electronic...

Page 14: ...When neutral is restored the alarm will NOT be muted automatically and the UPS will NOT go back to normal mode automatically ISO Compensation When UPS is connected to output isolation it will compensa...

Page 15: ...then utility restores the UPS will return to line mode Disable After Disable is set once UPS shutdown occurs and the utility restores the UPS will not automatically turn on Shutdown Delay Min UPS wil...

Page 16: ...ble ECO function Auto Restart Enable disable auto restart function PARAMETER information Parameter Information Page1 Line Voltage Range The acceptable line input voltage range Line FRE Range The accep...

Page 17: ...S operates in Bypass mode and supplies power to the load via the bypass NOTE When UPS is in Bypass mode the output voltage will draw power from utility after you switch on the input breaker In Bypass...

Page 18: ...may vary from different environment temperature and load type When setting backup time for 16 5 hours default value from LCD menu after discharging 16 5 hours UPS will shut down automatically to prote...

Page 19: ...nician that installed the UPS if you need to start parallel operations 3 5 1 Parallel system initial startup Please make sure that all of the running UPSs are parallel models and have the same configu...

Page 20: ...d in each UPS and then turn off the running system All UPSs will transfer to Bypass mode Remove all the maintenance bypass covers and set the maintenance switches from UPS to BPS position Turn off all...

Page 21: ...current in A phase 34 Synchronous trigger signal failure 75 INV IGBT over current in B phase 35 Parallel communication loss 76 INV IGBT over current in C phase 36 Parallel output current unbalance 77...

Page 22: ...UPS output and restart it Troubleshooting 4 Problem Possible cause Solutions Fault code is shown as 14 15 16 17 18 or 19 The UPS shut down automatically because short circuit occurs on the UPS output...

Page 23: ...capacitor such as BUS capacitors Only persons adequately familiar with batteries and with the required precautionary measures may replace batteries and supervise operations Unauthorized persons must...

Page 24: ...nt By ensuring this product is disposed of correctly you will help prevent potential negative consequences for the environment and human health which could otherwise be caused by inappropriate waste h...

Page 25: ......

Reviews: