background image

ORDERING INFORMATION

(blank)

SW2

SA

SA2

PA

PL  T24

Auto On (Switch Ch. 1) 
Auto On (Switch Ch. 2) 
Manual On (Switch Ch. 1) 
Manual On (Switch Ch. 2)
Auto On to 50% (Partial On)

1

Plug Load Control with Occ. only Tracking

2

(CA-T24 Plug Load)

(blank)

D

DS

None
0-10 VDC Dimming Output 
(via chase nipple)

0-10 VDC Dimming Output 
(via side slot)

Default Mode

Dimming

nPP16

Series

Power/Relay Pack 

nPP16

120/277 VAC 
347  VAC

Voltage

(blank)

347

(blank)

LT 

Standard
Low Temp

Temp/Humidity

C

US LISTED

ASSEMBLED in U.S.A.

WARRANTY  

5-year limited warranty. Complete warranty terms located at
www.acuitybrands.com/CustomerResources/Terms_and_conditions.aspx

TITLE 24 SYSTEM COMPONENT

 

√ Do not exceed maximum wattage, ratings, or published  

  operation conditions of product. 

 

√ Do not overload.

 

√ Follow all manufacturer’s warnings, recommendations  

  and restrictions to ensure proper operation of product.

• To reduce the risk of death, personal injury or property damage from fire, electric shock, falling parts, cuts/abrasions, and other hazards please read all warnings and instructions 

included with and on the fixture box and all fixture labels.  

•  Before installing, servicing, or performing routine maintenance upon this equipment, follow these general precautions.

•  Installation and service should be performed by a qualified licensed electrician.

•  Maintenance should be performed by qualified person(s) familiar with the products’ construction & operation & any hazards involved. Regular maintenance programs recommended.

READ AND FOLLOW ALL SAFETY INSTRUCTIONS!

SAVE THESE INSTRUCTIONS AND DELIVER TO OWNER AFTER INSTALLATION

 

•  

 DO NOT INSTALL DAMAGED PRODUCT! 

 This product has been properly packed so that no parts should have been damaged during transit. Inspect to confirm.  Any part damaged 

or broken during or after assembly should be replaced.

CAUTION: RISK OF PRODUCT DAMAGE

 

√ Electrostatic Discharge (ESD): ESD can damage product(s).  Personal grounding equipment should be worn  

  during all installation or servicing of the unit.

 

√ Do not touch individual electrical components, as this can cause ESD and affect product performance.

 

√ Do not stretch or use cable sets that are too short or are of insufficient length.

 

√ Do not tamper with contacts.

 

√ Do not modify the product.

 

√ Do not change or alter internal wiring or installation circuitry.

 

√ Do not use product for anything other than its intended use.

WARNING - RISK OF BURN or FIRE

        CAUTION - RISK OF INJURY

 

√ Wear gloves and safety glasses at all times when    

        installing, servicing or performing maintenance.

WARNING - RISK OF ELECTRIC SHOCK

 

√ Disconnect or turn off power before installation or servicing.

 

√ Verify that supply voltage is correct by comparing it with the  

  product information.

 

√ Make all electrical and grounded connections in accordance with      

  the National Electrical Code (NEC) and any applicable local code  

   requirements.

 

√ All wiring connections should be capped with UL approved      

  recognized wire connectors.

 

√ All unused connector openings must be capped.

Sensor Switch     900 Northrop Road, Wallingford, CT 06492     Phone: 1-800.PASSIVE      sensorswitch.com/nLight     ©2014 Acuity Brands Lighting, Inc.     All rights reserved 09/26/14

nPP16 Power / Relay Pack

Sheet#: TN-602-04

3 of 3

ELECTRICAL SPECS

OPERATING VOLTAGE

  120/277 VAC

  347 VAC (with -347 option)

MAX LOAD: (No derating necessary)

  16A  @ 120 VAC/ 277 VAC

  16A  @ 347 VAC (with -347 option)

MAX RECEPTACLE LOAD: 16A @ 120 VAC

MOTOR LOAD: 1 HP 

RELAY TYPE: Latching

FREQUENCY: 50/60 Hz

BUS OUPUT CURRENT/VOLTAGE:

  40mA / port @ 15 VDC

  (non-ER units only)

MAX DIMMING LOAD (with -D option): 

  Sinks 100 mA; 0-10 VDC dimmable 

ballasts or  LED drivers

nLIGHT NETWORK PORTS: (2) RJ-45

PHYSICAL SPECS

SIZE: (not incl. 1/2” chase nipple)

  3.38” H x 2.53” W x 1.83” D

  (8.59 cm x 6.43 cm x 4.65 cm)

WEIGHT: 6 oz

MOUNTING: 1/2” knockout

  (7/8” hole) on box or fixture

COLOR: 

  White (Standard)

  RED (-ER versions)

  BLUE (-PL T24 versions)

SPECIFICATIONS

ENVIRONMENTAL SPECS

OPERATING TEMP:

  Standard: 14º to 122º F (-10º to 50º C)

  LT Option: -40

º to 122º F (-40º to 50º C)

RELATIVE HUMIDITY:

  Standard: 20 to 75% non-condensing

  LT Option: 20 to 90% non-condensing

ROHS COMPLIANT

SILICONE FREE

UL 2043 Plenum Rated

None
UL924 Emergency 
Operation

Emergency

(blank)

ER

Note: For information on current monitoring relay packs, see the nPP16 IM series datasheet.

Notes:
1. Requires D or DS option