START-S5PV

Technical manual

-9-

 

Description of securities

The control unit dispose of inputs for 

CLOSING PHOTO-BEAM

 and 

STOP

. The first contact is activated only when the 

motor is closing or is in pause time; if this safety intervene while the motor is closing, the control unit stops and invert the 

motor until a new completely opening, while if the intervention is during the pause time it recharge the pause time and it 

doesn’t recluse. 

The input 

STOP

 is activated in any condition. If this input is not connected to the common input (terminal board 16-18) the 

control unit won’t accept any control and it stops immediately the motor if it is moving.

2.8  Connection of the PHOTO-BEAM

12     13      14     15      16     17      18     19      20     21      22     23     24      25

POWER SUPPLY TO

RX PHOTOCELL

Photocell 

receiver.

N.C. contact

POWER SUPPLY TO

TX PHOTOCELL

If the input 

PHOTO is not 

used, make a 

link (16-17)

2.9  Connection of the PHOTO-BEAM with PHOTO-TEST

12     13      14     15      16     17      18     19      20     21      22     23     24      25

POWER SUPPLY TO

TX PHOTOCELL

POWER SUPPLY TO

RX PHOTOCELL

Photocell 

receiver.

N.C. contact

ON

CTS

2

1

4

3

6

5

8

7

10

9

To activate the PHOTO-TEST put in 

ON the micro-switch 6 of DIPA

The contact of the receiver of the 

photo-beam should be:

- isolated from tensions

- normally closed

If you install more couple of photo-

beams make a serial connection.

The contact of the receiver of the 

photo-beam should be:

- isolated from tensions

- normally closed

If you install more couple of photo-

beams make a serial connection.

The photo-test make sure that the automation is working properly. The control unit will first do a test before opening. In case 

the installation of photo-beam is not good, the control unit will turn on the lamp for 5 seconds and the gate won’t working.

2.7  Power supply to accessories

Terminal Board 14-15

Power supply accessories

Tension: 

24Vac

Maximum current:

 300mA

12     13      14     15      16     17      18     19      

Common

Out +24 Vdc

Out +12 Vdc

Summary of Contents for START-S5PV

Page 1: ...art 24 Vac 24 Vac 19 18 17 16 15 14 13 12 22 21 20 24 23 Common 24 Antenna Opening limit switch 26 Input for opening control 28 Input for closing control 29 Closing limit switch 27 BRAKE Passive brake...

Page 2: ......

Page 3: ...of the TENSION 8 2 4 Connection of the LAMP 2 5 Connection of a 24V light for working and opening gate 2 6 Connection of a CONTACTOR 2 7 Power supply to accessories 9 2 8 Connection of the PHOTO BEAM...

Page 4: ...ssional installer Using the unit improperly and performing repairs or modifications personally will void the warranty The producer declines any responsibility for damages due to inappropriate use of t...

Page 5: ...te must be installed in proximity to the control unit If the motors do not have a cable use the 4 x 1 5 mm2 cable open close common ground In connecting the part with an extremely low safety voltage u...

Page 6: ...for services safeties Photo beam close 17 Input for photo beam the PHOTO will work only when closing Stop 18 Input for STOP Safety Edge 19 Input for SAFETY EDGE Pedestrian 20 Input for PARTIAL OPENIN...

Page 7: ...indicates that the micro processor is ac tivated and it is waiting for con trols WARNING This control can be used only with limit switches 1 2 230 Vac power supply of the control unit 1 3 400 Vac pow...

Page 8: ...p without flashing light card DIP 7 OFF In case the lamp has a flashing light control card 2 5 Connection of a 24V light for working and opening gate 12 13 14 15 16 30 31 Terminal board 14 15 Power su...

Page 9: ...sed make a link 16 17 2 9 Connection of the PHOTO BEAM with PHOTO TEST 12 13 14 15 16 17 18 19 20 21 22 23 24 25 POWER SUPPLY TO TX PHOTOCELL POWER SUPPLY TO RX PHOTOCELL Photocell receiver N C contac...

Page 10: ...LY OPEN contact You can connect a TIMER to plan the opening and closing time of the gate with the terminal board no 16 and 21 The contact should be NORMALLY OPEN and it should e closed for all time th...

Page 11: ...1 ON 2 ON When opening and when closing the motors stop and the invert at the next control IT RECLOSE AUTOMATICALLY 3 ON Inhibits the opening control It inhibits the opening control if the photo beam...

Page 12: ...230V output for lamp 7 OFF Lamp with electronic card It activate the flashing light of the electronic card of the lamp 230 V output for lamp 8 ON Delay in referse It activate a delay of 2 seconds befo...

Page 13: ...l the led TEST start flashing 3 Wait until the led TEST starts flashing 15 seconds 4 3 MEMORIZATION of a single remote control The memorization of a code is possible when the gate is CLOSED ON CTS 2 1...

Page 14: ...ART or 16 20 for opening of PARTIAL OPENING see CONNECTION OF AN OPENING CONTROL and CONNECTION OF A PARTIAL OPENING CONTROL or from a memorized remote control see MEMORIZATION OF A REMOTE CONTROL The...

Page 15: ...AUSA 5 Press PARTIAL OPENING to start closing L automazione parte in CHIUSURA 6 Wait that the gate stopping automatically L automazione in posizio ne di CHIUSO 7 Put in OFF the micro switch no 5 of DI...

Page 16: ...START S5PV Technical manual 16 6 Note...

Page 17: ...er countries regarding electric materials for use within certain voltage limits Reference to harmonized standards EN 60335 1 89 336 CE EEC DIRECTIVE 89 336 CE ISSUED BY THE EUROPEAN COUNCIL on May 3 1...

Page 18: ...on est pr sent e sous la seule responsabili du constructeur et si applica ble de son repr sentant autoris Busto Arsizio Va Italia 31 03 2010 ERNESTINO BANDERA Administrateur KONFORMIT TSZERTIFIKAT Der...

Page 19: ......

Page 20: ...1052 Busto Arsizio VA Italia tel 39 0331 683310 fax 39 0331 684423 posta ebtechnology it www ebtechnology it NOLOGO S r l via Cesare Cant 26 20020 Villa Cortese MI Italia tel 39 0331 430457 fax 39 033...

Reviews: