5 Parameters
BU 0500 EN-1516
127
Value Function
Description
Signal*
12
Value of P541
The output can be set using parameter P541 independently of the actual operating
status of the FI.
High
13
Generator torque current
limit
Limit value in P112 was reached in the generator range. Hysteresis = 10 %.
High
14
... 17 Reserved
--
18
FI ready
The FI is ready for operation. After being enabled it delivers an output signal.
High
19
… 29 reserved POSICON (BU 0510)
--
30
BusIO In Bit 0
Control by Bus In Bit 0 (P546 …)
High
31
BusIO In Bit 1
Control by Bus In Bit 1 (P546 …)
High
32
BusIO In Bit 2
Control by Bus In Bit 2 (P546 …)
High
33
BusIO In Bit 3
Control by Bus In Bit 3 (P546 …)
High
34
BusIO In Bit 4
Control by Bus In Bit 4 (P546 …)
High
35
BusIO In Bit 5
Control by Bus In Bit 5 (P546 …)
High
36
BusIO In Bit 6
Control by Bus In Bit 6 (P546 …)
High
37
BusIO In Bit 7
Control by Bus In Bit 7 (P546 …)
High
38
Value from Bus setpoint
Value from bus setpoint (P546 …)
High
Details can be found in the bus manuals
39
STO inactive
The relay / bit deactivates if STO or the Safe Stop are active.
High
40
reserved PLC (BU 0550)
* For relay contacts (High = "Contact closed", Low = "Contact open")
Pos: 273 /Anleitungen/Elektronik/FU und Starter/5. Parameter/Parameterüberschrift - Fortsetzung Tabelle @ 1\mod_1331566123473_388.docx @ 18340 @ @ 1
Parameter
{factory setting}
Setting value / Description / Note
Supervisor
Parameter
set
Pos: 274 /Anleitungen/Elektronik/FU und Starter/5. Parameter/Parameterauflistung (P000 ...)/P400-P499/Parameter P435 – Normierung Ausgang 1 (Relais 1 – MFR1) [SK 500...535E] @ 0\mod_1328001293364_388.docx @ 10273 @ @ 1
P435
Relay 1 scaling
(Scaling of output 1 (Relay 1
–
MFR1))
P
-400 ... 400 %
{ 100 }
Adjustment of the limit values of the relay function. For a negative value, the output function will
be output negative.
Reference to the following values:
Current limit (3) = x [%]
⋅
P203 >Rated motor current<
Torque current limit (4) = x [%]
⋅
P203
⋅
P206 (calculated rated motor torque)
Frequency limit (5) = x [%]
⋅
P201 >Rated motor frequency<
Pos: 276 /Anleitungen/Elektronik/FU und Starter/5. Parameter/Parameterauflistung (P000 ...)/P400-P499/Parameter P436 – Hysterese Ausgang 1 (Relais 1 – MFR1) [SK 500...535E] @ 0\mod_1328001508896_388.docx @ 10319 @ @ 1
P436
Relay 1 hysteresis
(Hysteresis of output 1 (Relay 1
–
MFR1))
S
P
1 ... 100 %
{ 10 }
Difference between switch-on and switch-off point to prevent oscillation of the output signal.
Pos: 278 /Anleitungen/Elektronik/FU und Starter/5. Parameter/Parameterauflistung (P000 ...)/P400-P499/Parameter P441 – Funktion Ausgang 2 (Relais 2 - MFR2) [SK 500...535E] @ 0\mod_1328001637835_388.docx @ 10365 @ @ 1
P441
Relay 2 function
(Function of output 2 (Relay 2
–
MFR2))
P
0 ... 39
{ 7 }
Control terminals 3/4:
Functions are identical to P434!
Pos: 279 /Anleitungen/Elektronik/FU und Starter/5. Parameter/Parameterauflistung (P000 ...)/P400-P499/Parameter P442 – Normierung Ausgang 2 (Relais 2 - MFR2) [SK 500...535E] @ 0\mod_1328001691836_388.docx @ 10388 @ @ 1
P442
Relay 2 scaling
(Scaling of output 2 (Relay 2
–
MFR1))
P
-400 ... 400 %
{ 100 }
Functions are identical to P435!