5 Parameters
BU 0500 EN-1516
133
Additional parameters
Parameter
{factory setting}
Setting value / Description / Note
Supervisor
Parameter set
Pos: 303 /Anleitungen/Elektronik/FU und Starter/5. Parameter/Parameterauflistung (P000 ...)/P500-P599/Parameter P501 – Umrichtername @ 0\mod_1328091645446_388.docx @ 10904 @ @ 1
P501
[-01]
...
[-20]
Inverter name
(Inverter name)
A…Z
(char)
{ 0 }
Free input of a designation (name) for the device (max. 20 characters). With this, the frequency
inverter can be uniquely identified for setting with NORD CON software or within a network.
Pos: 304 /Anleitungen/Elektronik/FU und Starter/5. Parameter/Parameterauflistung (P000 ...)/P500-P599/Parameter P502 – Wert Leitfunktion [SK 5xxE] @ 0\mod_1328091690836_388.docx @ 10927 @ @ 1
P502
[-01]
...
[-05]
Value Masterfunction
(Value master function)
S
P
0 ... 57
{ all 0 }
Selection of the master value of a Master for output to a bus system (see P503) - (up to SK 535E:
max. 3 master values, SK 540 and above: max. 5 master values). The assignment of these
master values to the slave is carried out via (P546) (...(P548)):
[-01] =
Master value 1
[-02] =
Master value 2
[-03] =
Master value 3
SK 540E and above:
[-04] =
Master value 4
[-05] =
Master value 5
Selection of possible setting values for master values:
00 =
Off
01 =
Actual frequency
02 =
Actual speed
03 =
Electricity
04 =
Torque current
05 =
State digital-IO
06 =
Reserved
07 =
Reserved
08 =
Set point frequency
09 =
Error code
10 =
Reserved
11 =
Reserved
12 =
BusIO Out Bits 0-7
13 =
Reserved
14 =
Reserved
15 =
Reserved
16 =
Reserved
17 =
Value analog input 1
18 =
Value analog input 2
19 =
Frequency master
value
20 =
Setpoint freq. after
ramp
21 =
Actual freq. w/o slip
22 =
Speed encoder
23 =
Actual freq. with slip
(SW V2.0 and above)
24 =
Act. freq. with slip
(SW V2.0 and above)
53 =
... 57 Reserved
NOTE:
For details regarding the processing of setpoints and actual values, pleas refer to
Section 8.7.
Pos: 305 /Anleitungen/Elektronik/FU und Starter/5. Parameter/Parameterauflistung (P000 ...)/P500-P599/Parameter P503 – Leitfunktion Ausgabe @ 0\mod_1328091743696_388.docx @ 10950 @ @ 1
P503
Master function output
(Master function output)
S
0 ... 5
{ 0 }
For master-slave applications this parameter specifies on which bus system the master transmits
the control word and the master values (P502) for the slave. On the slave, parameters (P509),
(P510), (P546 ... ) define the source from which the slave obtains the control word and the master
values from the master and how these are to be processed by the slave.
0 = Off:
no output of control word and master values.
1 = USS:
output of control words and master values to USS.
2 = CAN:
output of control words and master values to CAN (up to
250 kBaud).
3 = CANopen:
output of control words and master values to CANopen.
4 = System bus active:
no output of control word and master values, however via the
ParameterBox or NORD CON, all participants which are set to
System bus active
are visible.
5 = Sys.bus active:
output of control word and master values on CAN open via the
ParameterBox or NORD CON, all participants which are set to
system bus active
are visible.
Summary of Contents for BU 0500
Page 1: ...EN BU 0500 SK 500E Users Manual for Frequency Inverters ...
Page 211: ......
Page 212: ...6075002 3021 ...