SK 500E – Users Manual for Frequency Inverters
150
BU 0500 EN-3021
Information
Parameter
Setting value / Description / Note
Supervisor
Parameter set
Pos: 377 /Anleitungen/Elektronik/FU und Starter/5. Parameter/Parameterauflistung (P000 ...)/P700-P799/Parameter P700 – Aktueller Betriebszustand @ 0\mod_1328170483810_388.docx @ 12318 @ @ 1
P700
[-01]
...
[-03]
Actual operating status
(Actual operating status)
0.0 ... 25.4
Display of current messages for the present operating status of the frequency inverter such as
faults, warnings or the reason why switch-on is disabled (please see chapter 6 "Operating status
messages").
[-01] = Present fault,
shows the currently active (unacknowledged) fault (please see section
[-02] = Present warning,
indicates a current warning message (please see section "Warning
[-03] = Reason for disabled starting,
indicates the reason for an active start disable (please see
section "Switch-on block messages").
NOTE
SimpleBox / ControlBox:
the error numbers of the warning messages and faults can be displayed
using SimpleBox and ControlBox.
ParameterBox:
with the ParameterBox the messages are displayed in plain text.. In addition, the
reason for a possible disabling of starting can also be displayed.
Bus:
The display of bus-level error messages is displayed in decimal integer format. The
displayed value must be divided by 10 in order to correspond with the correct format.
Example: Display: 20 → Error number: 2.0
Pos: 378 /Anleitungen/Elektronik/FU und Starter/5. Parameter/Parameterauflistung (P000 ...)/P700-P799/Parameter P701 – Letzte Störung 1...5 @ 0\mod_1328170536746_388.docx @ 12341 @ @ 1
P701
[-01]
...
[-05]
Last fault 1 ... 5
(Last fault 1...5)
0.0 ... 25.4
This
parameter stores the last 5 faults
(please see section "Error messages").
The SimpleBox / ControlBox must be used to select the corresponding memory location 1...5-
(Array parameter), and confirmed using the OK / ENTER key to read the stored error code.
Pos: 379 /Anleitungen/Elektronik/FU und Starter/5. Parameter/Parameterauflistung (P000 ...)/P700-P799/Parameter P702 – Frequenz letzte Störung 1...5 @ 0\mod_1328170589463_388.docx @ 12364 @ @ 1
P702
[-01]
...
[-05]
Last frequency error
(Last frequency error 1...5)
S
-400.0 ... 400.0 Hz
This parameter stores the output frequency that was being delivered at the time the fault occurred.
The values of the last 5 errors are stored.
The SimpleBox / ControlBox must be used to select the corresponding memory location 1...5-
(Array parameter), and confirmed using the OK- / ENTER key to read the stored error code.
Pos: 380 /Anleitungen/Elektronik/FU und Starter/5. Parameter/Parameterauflistung (P000 ...)/P700-P799/Parameter P703 – Strom letzte Störung 1...5 @ 0\mod_1328170627489_388.docx @ 12387 @ @ 1
P703
[-01]
...
[-05]
Current last error
(Last current error 1...5)
S
0.0 ... 999.9 A
This parameter stores the output current that was being delivered at the time the fault occurred.
The values of the last 5 errors are stored.
The SimpleBox / ControlBox must be used to select the corresponding memory location 1...5-
(Array parameter), and confirmed using the OK / ENTER key to read the stored error code.
Pos: 381 /Anleitungen/Elektronik/FU und Starter/5. Parameter/Parameterauflistung (P000 ...)/P700-P799/Parameter P704 – Spannung letzte Störung 1...5 @ 0\mod_1328170671391_388.docx @ 12410 @ @ 1