7.9 Information
BU 0750 GB
Technical design subject to change
119
7.9 Information
Parameter
Setting value / Description / Note
Parameter
set
Available with option
P700
Current fault
Always available
0.0 ... 20.9
A fault currently being reported. Fore more details see Section 6, Error signals.
ControlBox:
A description of the meaning of the various error numbers will be found in the
"Error messages" section.
ParameterBox:
Faults are displayed in clear text, more information is provided in the section
where the error messages are discussed.
P701
.. - 01
...
.. - 05
Last fault 1...5
Always available
0.0 ... 20.9
This parameter ensures that the past 5 incidents are stored. For more details see Section 6, Er-
ror signals.
When the ControlBox is used, the memory locations 1 to 5 (array) assigned to these faults must
be accessed and validated with the ENTER command for the stored error code to be readable.
P702
.. - 01
...
.. - 05
Frequ. last error 1...5
Always available
-400.0 ... 400.0 Hz
This parameter stores the output frequency supplied the moment the incident occurred. The
frequency vallues of the past 5 errors are stored.
When the ControlBox is used, the memory locations 1 to 5 (array) assigned to these faults must
be accessed and validated with the ENTER command for the stored error code to be readable.
P703
.. - 01
...
.. - 05
Current. last erro 1...5
Always available
0.0 ... 500.0 A
This parameter stores the output current supplied the moment the incident occurred. The cur-
rent values of the past 5 errors are stored.
When the ControlBox is used, the memory locations 1 to 5 (array) assigned to these faults must
be accessed and validated with the ENTER command for the stored error code to be readable.
P704
.. - 01
...
.. - 05
Volt. last error 1...5
Always available
0 ... 500 V AC
This parameter stores the output voltage supplied the moment the incident occurred. Thje volt-
age values of the past 5 errors are stored.
When the ControlBox is used, the memory locations 1 to 5 (array) assigned to these faults must
be accessed and validated with the ENTER command for the stored error code to be readable.
P705
.. - 01
...
.. - 05
Dc.Ink volt.last e 1...5
Always available
0 ... 1000 V DC
This parameter stores the d.c. link voltage supplied the moment the incident occurred. The volt-
age values of the past 5 errors are stored.
When the ControlBox is used, the memory locations 1 to 5 (array) assigned to these faults must
be accessed and validated with the ENTER command for the stored error code to be readable.