4 Commissioning
BU 0200 en-US-4920
129
Pos : 269. 36 / Anl eit ungen/ Elektronik/FU und St arter/ 4. I nbetriebnahm e/AS-I nt erface [all e Ger ät e]/ Adr essi erung_01 [SK 1xx E, SK 2xxE, SK 1xx E-FDS] @ 9\mod_1444202497668_14638. doc x @ 248675 @ 4 @ 1
4.5.4.4
Addressing
In order to use the device in an AS-i network, it must have a unique address. The address is set to 0 in
the factory. This means that the device can be recognized as a "new device" by an AS-i master
(prerequisite for automatic address assignment by the master).
Procedure
• Ensure power supply of the AS interface via the yellow AS interface cable.
• Disconnect the AS interface master during addressing
•
Set the address ≠ 0
• Do not doubly assign addresses
In many other cases, addressing is carried out using a normal addressing device for AS- interface
slaves (example follows).
• Fuchs, VBP-HH1-V3.0-V1 (separate M12 connection for external power supply)
• IFM, AC1154 (battery operated addressing device)
Pos : 269. 37 / Anl eit ungen/ Elektronik/FU und St arter/ 4. I nbetriebnahm e/AS-I nt erface [all e Ger ät e]/ Adr essi erung_02 [SK 2xx E] @ 9\m od_1444206061104_14638. docx @ 248707 @ @ 1
Information
Special conditions for SK 2x5E
Does not apply to special versions …-AUX and –AXB
•
Also provide voltage supply of variable frequency drive via the yellow AS- interface line (pay attention to
power consumption of control level of variable frequency drive (290 mA))
•
When using an addressing device
– Do not use the internal voltage source of the addressing device
– Battery-operated addressing devices do not supply the current that is needed and are therefore unsuitable
– Use addressing unit with a separate 24 V DC connection for an external power supply (example:
Fuchs, VBP-HH1-V3.0-V1)
The options for addressing the AS-i slave with an addressing unit in practice are listed below.
Pos : 269. 38 / Allgemei n/ Allgemei ngültige M odul e/---------Seitenum bruch kom pakt --------- @ 13\m od_1476369695906_0.docx @ 2265496 @ @ 1