5 Parameter
BU 0200 en-US-4920
195
Pos : 515 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P500- P599/Param et er P523 – Werks einst ellung [SK 1x 0E, SK 2xx E, SK 250E-FD S] @ 59\mod_1606918747165_14638. doc x @ 2703057 @ @ 1
P523
Factory setting
(factory setting)
0 ... 3
{ 0 }
By selecting the appropriate value and confirming it with the Enter key, the selected parameter
range is entered in the factory setting. Once the setting has been made, the value of the
parameter automatically returns to 0.
0 = No change:
Does not change the parameterization.
1 = Load factory setting:
The complete parameterization of the VFD reverts to the factory
setting. All originally parameterized data are lost.
2 = Fact.setng.w.out bus
All parameters of the variable frequency drive, but not the bus
parameters, are reset to the factory setting.
3 = Fact set w/o motor
All parameters of the variable frequency drive, but not the motor
data parameters (P201 ... P209, P240 ... P246), are reset to the factory setting.
Pos : 516 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P500- P599/Param et er P523 – Werks einst ellung_Ergänz ung Einst ellung 3 [SK 2xx E, SK 250E-FD S] @ 59\mod_1606917961246_14638. doc x @ 2703020 @ @ 1
Up to firmware version V 2.2 R0 also the PMSM-relevant parameters (
P240
to
P246
)
have been reset. This does no longer apply to the current firmware. The parameter
settings of these parameters now also remain unchanged.
Pos : 517 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P500- P599/Param et er P523 – Werks einst ellung_Ergänz ung [SK 2xx E] @ 9\m od_1448294698250_14638. docx @ 266034 @ @ 1
Note:
If an external EEPROM ("memory module") is plugged in, then a value of ("Factory setting
…") only affect this. If no "memory module" is present, the set command ("Factory setting …") is
applied to the internal EEPROM
Pos : 518 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P500- P599/Param et er P525 – Last überw ac hung Maximalwer t @ 0\mod_1328093087228_14638.docx @ 15065 @ @ 1
P525
[-01]
...
[-03]
Load control max.
(load monitoring, maximum value)
S
P
1 ... 400%/401
{ all 401 }
Selection of up to 3 auxiliary values:
[-01] = Auxiliary value 1
[-02] = Auxiliary value 2
[-03] = Auxiliary value 3
Maximum load torque value.
Setting of the upper limit of load monitoring. Up to 3 values can be specified. Prefixes are not
taken into account, only the integer values are processed (motor/generator torque, right/left
rotation). The array elements [-01], [-02] and [-03] of parameters (P525) … (P527), or the entries
which are made there always belong together.
401 = OFF
Means that the function is switched off. No monitoring is performed. This is also the
basic setting for the VFD.
Pos : 519 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P500- P599/Param et er P526 – Last überw ac hung Minim alwert @ 0\m od_1328093137197_14638.docx @ 15066 @ @ 1
P526
[-01]
...
[-03]
Load control min.
(load monitoring, minimum value)
S
P
0 ... 400 %
{ all 0 }
Selection of up to 3 auxiliary values:
[-01] = Auxiliary value 1
[-02] = Auxiliary value 2
[-03] = Auxiliary value 3
Minimum load torque.
Setting of the lower limit of load monitoring. Up to 3 values can be specified. Prefixes are not
taken into account, only the integer values are processed (motor/generator torque, right/left
rotation). The array elements [-01], [-02] and [-03] of parameters (P525) … (P527), or the entries
which are made there always belong together.
0 = OFF
Means that the function is switched off. No monitoring is performed. This is also the
basic setting for the VFD.