5.6
Additional parameters
BU 0500 GB
Subject to technical alterations
109
Parameter
Set value / Description / Note
Device
Supervisor
Parameter
set
P540
Rotation direction mode
S P
0 ... 7
[ 0 ]
For safety reasons this parameter can be used to prevent a rotation direction reversal and
therefore the incorrect rotation direction.
This function does not work with active position control (SK 53xE only, P600
≠
0).
0 = No rotation direction limitation
1 = Block direction reversal
, the direction reverse button of the ControlBox
SK TU3-CTR is blocked.
2 = CW only*,
only clockwise direction is possible. The selection of the "incorrect" rotation
direction leads to the output of the minimum frequency P104 with the field of rotation R.
3 = CCW only*,
only counter-clockwise direction is possible. The selection of the "incorrect"
rotation direction leads to the output of the minimum frequency P104 with the field of
rotation L.
4 = Enable direction only,
rotation direction is only possible according to the enable signal,
otherwise 0Hz is output.
5 = CW only monitored*,
only CW rotation is possible. The selection of the "incorrect"
rotation direction leads to the FI switching off (control block). If necessary, an adequately
large setpoint value (>f
min
) must be observed.
6 = CCW only monitored*,
only CCW rotation is possible. The selection of the "incorrect"
rotation direction leads to the FI switching off (control block). If necessary, an adequately
large setpoint value (>f
min
) must be observed.
7 = Enable direction only monitored,
Rotation direction is only possible according to the
enable signal, otherwise the FI is switched off.
*) Applies to keyboard (SK TU3-) and control terminal actuation,
in addition, the direction key on the ControlBox is blocked.
P541 Set
Output
S
This function provides the opportunity to control the relay and the digital outputs independently of
the frequency inverter status. To do this, the relevant output must be set to the function "External
control".
This function can either be used manually or in combination with a bus control.
Bit 0 = Output 1 (K1)
Bit 1 = Output 2 (K2)
Bit 2 = Output 3 (DOUT1)
Bit 3 = Output 4 (DOUT2)
Bit 4 = Dig. AOut 1
(Analog output 1)
Bit 5 … 7 =
reserved
Bit 8 = Bus Out Bit 0
Bit 9 = Bus Out Bit 1
Bit 10 = Bus Out Bit 2
Bit 11 = Bus Out Bit 3
Bit 12 = Bus Out Bit 4
Bit 13 = Bus Out Bit 5
Bit 13 -12
Bit 11 -8
Bit 7 -4
Bit 3 -0
Min. Value
00
0
0000
0
0000
0
0000
0
Binary
hex
Max. Value
11
3
1111
F
0001
1
1111
F
Binary
hex
0000 ... 3F1F (hex)
[ 0000 ]
BUS:
The corresponding hex value is written into the parameter, thereby setting the
relay and digital outputs.
ControlBox:
The hexadecimal code is entered directly when the ControlBox is used.
ParameterBox:
Each individual output can be separately called up in plain text and activated.