5.8
Information
BU 0500 GB
Subject to technical alterations
115
Parameter
Set value / Description / Note
Device
Supervisor
Parameter
set
P705
... - 01
...
... - 05
UZW previous fault 1...5
S
0 ... 1000 V DC
This parameter stores the link voltage that was being delivered at the time the error occurred. The
values of the last 5 errors are stored.
The ControlBox must be used to select the corresponding memory location 1...5- (Array
parameter), and confirmed using the ENTER key to read the stored error code.
P706
... - 01
...
... - 05
Parameter set previous fault 1...5
S
0 ... 3
This parameter stores the parameter set code that was active when the error occurred. Data for
the previous 5 faults are stored.
The ControlBox must be used to select the corresponding memory location 1...5- (Array
parameter), and confirmed using the ENTER key to read the stored error code.
P707
... - 01
...
... - 03
Software version/ revision
0.0 ... 9999.9
This parameter shows the software and revision
numbers in the FI. This can be significant when
different FIs are assigned the same settings.
Array 03 provides information about any special
versions of the hardware or software A zero
stands for the standard version.
... - 01 =
Version number (1.7)
... - 02 =
Revision number (R0)
... - 03 =
Special version of
hardware/software (0.0)
P708
Status of digital inputs
(SK 520E)
Displays the status of the digital inputs in binary/hexadecimal code. This display can be used to
check the input signals.
Bit 0 =
Digital input 1
Bit 1 =
Digital input 2
Bit 2 =
Digital input 3
Bit 3 =
Digital input 4
Bit 4 =
Digital input 5
Bit 5 =
Digital input 6 (SK 52x/53xE)
Bit 6 =
Digital input 7 (SK 52x/53xE)
Bit 7 =
Digital function analog input 1
Bit 8 =
Digital function analog input 2
Bit 11-8
Bit 7-4
Bit 3-0
Minimum value
0000
0
0000
0
0000
0
binary
hex
Maximum value
0001
1
1111
F
1111
F
binary
hex
000000000 ...
111111111 (binary)
or
0000 ... 01FF
(hexadecimal)
ControlBox:
the binary Bits are converted into a hexadecimal value and displayed.
ParameterBox:
the Bits are displayed increasing from right to left (binary).
P709
Voltage analog input 1
0.00 ... 10.00 V
Displays the measured analog input value 1.
P710
Voltage analog output
0.0 ... 10.0 V
Displays the delivered value of analog output 1. (0.0 ... 10.0V)