130
Subject to technical alterations
BU 0500 GB
Display
in the ControlBox
Group
Detail in
P700 / P701
Error
text in the Parameter Box
Cause
•
Remedy
8.0
EEPROM parameter loss
(maximum value exceeded) )
Error in EEPROM data
•
Software version of the stored data set not compatible
with the software version of the FI.
NOTE:
Faulty
parameters
are automatically reloaded
(factory setting).
•
EMC interferences (see also E020)
8.1
Invalid inverter type
•
EEPROM
faulty
8.2
External EEPROM copy error
(ControlBox)
•
Check ControlBox for correct position.
•
ControlBox EEPROM faulty (P550 = 1).
8.3 Customer
interface
incorrectly identified
(customer’s interface
equipment)
8.4 Database
version
incorrect
E008
8.7
Original and mirror not
identical
The upgrade level of the frequency inverter was not correctly
identified.
•
Switch mains voltage off and on again.
E009
---
ControlBox error/ SimpleBox
error
SPI Bus faulty, no communication with ControlBox /
SimpleBox.
•
Check ControlBox for correct position.
•
Check correct cabling of SimpleBox.
•
Switch mains voltage off and on again.
10.0 Telegram
downtime
Data transfer is faulty. Check P513
•
Check external Bus connection.
•
Check Bus Protocol program process.
•
Check Bus master.
•
Check 24V supply of internal CAN/CANopen Bus.
•
Nodeguarding
error (internal CANopen)
•
Bus Off
error (internal CAN Bus)
10.2
External bus module
telegram time-out
Telegram transfer is faulty.
•
Check external connection.
•
Check Bus Protocol program process.
•
Check Bus master.
10.4
External bus module
initialisation failure
•
Check
P746.
•
Bus module not correctly plugged in.
•
Check Bus module current supply.
10.1
10.3
10.5
10.6
10.7
External Bus module system
failure
Further details can be found in the respective additional BUS
operating instructions.
E010
10.8 External
module
communication failure
Connection fault / error in the external component